PT-IQ-3-PB+F-UT - Surge protection device


Notes | General Note: Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
Product properties | IEC test classification: C1 C2 C3 D1 Type: DIN rail module, two-section, divisible Product type: Surge protection for information technology Product family: PLUGTRAB IQ Surge protection fault message: Optical, multi-stage Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal voltage UN: 5 VÃDC |
Connection data | Connection method: Screw connection Screw thread: M3 Tightening torque: 0.5 Nm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/fc46ccf10e2bae4da270189f6d2038dc/-S204x204-FJPG Width: 17.7 mm Height: 91.1 mm Depth: 77.5 mm (incl. DIN rail 7.5Ãmm) Horizontal pitch: 1 Div. |
Material specifications | Flammability rating according to UL 94: V-0 Housing material: PA 6.6 |
Mechanical properties | Mechanical data Open side panel: No |
Protective circuit | Direction of action: Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground Maximum continuous voltage UC: 6 VÃDC 4 VÃAC Rated current: 600 mA (40ðC) Operating effective current IC at UC: ââ°¤ 800 õA (per path) Residual current IPE: ââ°¤ 10 õA Nominal discharge current In (8/20) õs (line-line): 10 kA Nominal discharge current In (8/20) õs (line-ground): 10 kA Pulse discharge current Iimp (10/350)Ãõs (line-earth): 2.5 kA Pulse discharge current Iimp (10/350)Ãõs (line-signalground): 2.5 kA Total discharge current Itotal (8/20)Ãõs: 20 kA Voltage protection level Up (line-line): ââ°¤ 90 V (C1 - 1ÃkV / 500ÃA) ââ°¤ 140 V (C2 - 10 kV / 5 kA) ââ°¤ 30 V (C3 - 25ÃA) ââ°¤ 30 V (C3 - 50ÃA) Voltage protection level Up (line-earth): ââ°¤ 730 V (C1 - 1ÃkV / 500ÃA) ââ°¤ 900 V (C2 - 10 kV / 5 kA) ââ°¤ 900 V (C3 - 25ÃA) ââ°¤ 900 V (C3 - 50ÃA) Voltage protection level Up (line-signalground): ââ°¤ 90 V (C1 - 1ÃkV / 500ÃA) ââ°¤ 140 V (C2 - 10 kV / 5 kA) ââ°¤ 30 V (C3 - 25ÃA) ââ°¤ 30 V (C3 - 50ÃA) Voltage protection level Up static (line-line): ââ°¤ 45 V (C1 - 1ÃkV / 500ÃA) Voltage protection level Up static (line-signalground): ââ°¤ 45 V (C1 - 1ÃkV / 500ÃA) Response time tA (line-line): ââ°¤ 1 ns Response time tA (line-earth): ââ°¤ 100 ns Response time tA (line-signalground): ââ°¤ 1 ns Input attenuation aE, sym.: typ. 0.3 dB (ââ°¤ 10 MHz/150 é) Input attenuation aE, asym.: typ. 0.3 dB (ââ°¤ 10 MHz/150 é) Cut-off frequency fg (3ÃdB), sym. in 150Ãé system: typ. 60 MHz Cut-off frequency fg (3ÃdB), asym. (signal ground) in 150Ãé system: typ. 60 MHz Capacity (Core-Core): typ. 30 pF Capacity (line-signalground): typ. 30 pF Resistance per path: 1.2 é ñ5Ã% Surge protection fault message: Optical, multi-stage Max. required back-up fuse: 600 mA (FF) Impulse durability (line-line): C1 - 1ÃkV / 500ÃA C2 - 10ÃkV / 5ÃkA C3 - 50ÃA Impulse durability (line-earth): C1 - 1ÃkV / 500ÃA C2 - 10ÃkV / 5ÃkA C3 - 50ÃA D1 - 2.5ÃkA Impulse durability (line-signalground): C1 - 1ÃkV / 500ÃA C2 - 10ÃkV / 5ÃkA C3 - 50ÃA D1 - 2,5ÃkA Pulse reset time (line-line): ââ°¤ 10Ãms Pulse reset time (line-earth): ââ°¤ 10Ãms Pulse reset time (line-signalground): ââ°¤ 10Ãms |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ââ°¤ 4000 m (amsl) |
Standards and regulations | Standards/specifications: IEC 61643-21 ENÃ61643-21 ENÃ61000-6-2 ENÃ61000-6-3 Note: 2000 + A1:2008 + A2:2012 2001 + A1:2009 2007 + A1:2011 2005 |
Mounting | Mounting type: DIN rail: 35 mm |