Industrial Automation
PT-IQ-2X2-EX-24DC-UT - Surge protection device


Product properties | IEC test classification: C1 C2 C3 D1 Type: DIN rail module, two-section, divisible Product type: Surge protection for MCR technology Product family: PLUGTRAB IQ Wire pairs per module: 2 Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal voltage UN: 24 VÃDC Indicator/remote signaling Switching function: via DIN rail connector |
Connection data | Connection method: Screw connection Screw thread: M3 Tightening torque: 0.5 Nm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 |
Ex data | Maximum inner capacitance Ci: negligible Max. internal inductance Li: negligible Max. input current Ii: 350 mA Max. input voltage Ui: 30 VÃDC max. input power Pi: 1.2 W Insulation voltage to ground: > 500 VÃAC Ambient temperature (operation): -40°C ... 50°C (T6) -40°C ... 70°C (T4) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/fc46ccf10e2bae4da270189f6d2038dc/-S204x204-FJPG Width: 17.7 mm Height: 91.1 mm Depth: 77.5 mm (incl. DIN rail 7.5Ãmm) Horizontal pitch: 1 Div. |
Material specifications | Flammability rating according to UL 94: V-0 Insulating material: PA 6.6 Housing material: PA 6.6 |
Mechanical properties | Mechanical data Open side panel: No |
Protective circuit | Direction of action: Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground Maximum continuous voltage UC: 30 VÃDC 21 VÃAC Rated current: 350 mA Operating effective current IC at UC: ââ°¤ 5 õA (per system) Residual current IPE: ââ°¤ 100 nA (per system) Nominal discharge current In (8/20) õs (line-line): 10 kA Nominal discharge current In (8/20) õs (line-ground): 10 kA Pulse discharge current Iimp (10/350)Ãõs (line-earth): 2 kA Total discharge current Itotal (8/20)Ãõs: 20 kA Voltage protection level Up (line-line): ââ°¤ 60 V (C1 - 1ÃkV / 500ÃA) ââ°¤ 110 V (C2 - 10 kV / 5 kA) ââ°¤ 140 V (C2 - 10ÃkA) ââ°¤ 50 V (C3 - 25ÃA) ââ°¤ 55 V (C3 - 100ÃA) Voltage protection level Up (line-earth): ââ°¤ 1.3 kV (C2 - 10 kV / 5 kA) ââ°¤ 1.5 kV (C2 - 10ÃkA) ââ°¤ 1.3 kV (C3 - 100ÃA) Response time tA (line-line): ââ°¤ 1 ns Response time tA (line-earth): ââ°¤ 100 ns Input attenuation aE, sym.: typ. 0.3 dB (ââ°¤ 300 kHz / 150 é) Cut-off frequency fg (3ÃdB), sym. in 150Ãé system: typ. 1.1 MHz Capacity (Core-Earth): typ. 2 nF Resistance per path: 1.2 é ñ5Ã% Surge protection fault message: Optical, multi-stage Max. required back-up fuse: 350 mA (F) Impulse durability (line-line): C1 - 1ÃkV / 500ÃA C2 - 10ÃkA C3 - 100ÃA Impulse durability (line-earth): C2 - 10ÃkA D1 - 2ÃkA Pulse reset time (line-line): ââ°¤Ã30Ãms Pulse reset time (line-earth): ââ°¤ 30Ãms |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ââ°¤ 2000 m (amsl) |
Approvals | Conformity/Approvals UL, USA / Canada: Class I, Div. 2, Groups A, B, C, D T5 |
Standards and regulations | Standards/specifications: ENÃ61643-21 IEC 61643-21 ENÃ61000-6-2 ENÃ61000-6-3 ENÃ60079-0 ENÃ60079-11 ENÃ60079-15 IEC 60079-0 IEC 60079-11 IEC 60079-15 Note: A2:2013 A2:2012 2005 A1:2011 2018 2012 2010 2017 2011 2010 |
Mounting | Mounting type: DIN rail: 35 mm |
Description other products