Industrial Automation
Expansion Module(EM), Guardmaster, Monitoring Safety Relay, Single Wire Safe Only Input, 1 N.C. Solid State Auxiliary Outputs







| Number of outputs, safety related, undelayed, with contact | 4 | 
| Number of outputs, safety related, delayed, with contact | 0 | 
| Number of outputs, signalling function, undelayed, with contact | 0 | 
| Number of outputs, safety related, undelayed, semiconductors | 0 | 
| Number of outputs, safety related, delayed, semiconductors | 0 | 
| Number of outputs, signalling function, undelayed, semiconductors | 0 | 
| Number of outputs, signalling function, delayed, semiconductors | 0 | 
| With start input | No | 
| With muting function | No | 
| Voltage type for actuating | DC | 
| Rated control supply voltage at DC | 24 V | 
| Model | Expansion device | 
| Type of electric connection | Screw connection | 
| Evaluation inputs | Other | 
| Power consumption | 3.5 W | 
| Safety output rating | 2 A @ 24V DC (0.1 Hz), DC-13 (UL: B300) | 
| Wire size | 0.2 to 2.5 mmò | 
| Number of outputs, signalling function, delayed, with contact | 0 | 
| With feedback circuit | Yes | 
| Aggregate current of outputs per module, max | 6 A | 
| Surge output current duration, max | 5 ms | 
| Continuous output current, max | 50 mA | 
| Surge output current, max | 700 mA | 
| Other input | SWS input | 
| Other output | SWS output | 
| Operating voltage | 20.4 V | 
| SIL according to IEC 61508 | 3 | 
| With approval according to UL | Yes | 
| Stop category according to IEC 60204 | 0 | 
| Performance level according to EN ISO 13849-1 | Level e | 
| Type of safety according to IEC 61496-1 | 4 | 
| With approval for TUV | Yes | 
| With detachable clamps | Yes | 
| Rated control supply voltage at AC 50 Hz | 0 V | 
| Rated control supply voltage at AC 60 Hz | 0 V | 
| Mechanical life operations | 10000000 | 
| Vibration | 10...55 Hz, 0.35 mm | 
| Shock | 10 g, 16 ms | 
| Release-delay | 0 s | 
| Rail mounting possible | Yes | 
| Enclosure protection | IP40 (NEMA 1) | 
| Safe failure fraction | 99 % | 
| PFHd | 1.81 E-09 | 
| Mode of operation | High demand mode | 
| Category | Up to 4 | 
| Hardware fault tolerance | 1 | 
| MTTFd | 190 year | 
| DC avg | 99 % | 
| T cycle | 8 hr/8.28 s | 
| Mission time | 20 year | 
| Hours of operation | 24 h | 
| Days of operation | 365 Days | 
| Performance level | Up to e | 
| Evaluation input | SWS input | 
| Operating temperature | -5 ðC | 
| Relative humidity | 90% | 
| Height | 119.14 mm | 
| Width | 22.5 mm | 
| Depth | 113.6 mm | 
Description other products