Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

ROCKWELL AUTOMATION 2080-MOT-HSC
ROCKWELL AUTOMATION 2080-MOT-HSC
ROCKWELL AUTOMATION 2080-MOT-HSC
ROCKWELL AUTOMATIONAvailable

Micro800 250KHz HSC Plug-In

2080 Micro800 System, High Speed Counter, 4 inputs with Line Driver, 250KHz
Product Code: 2080-MOT-HSC
Partner cod.: 2080-MOT-HSC
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Tecnichal data
Time delay at signal exchange2 ms
Suitable for safety functionsYes
Digital inputs configurableYes
Digital outputs configurableYes
Type of voltage (input voltage)DC
Type of output voltageDC
Type of digital outputOther
Type of electric connectionScrew connection
Wiring category2 - on signal ports
Wire sizeSolid: 0.14 mm2 (26 AWG)...1.5 mm2 (16 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 (26 AWG)...1.0 mm2 (18 AWG) @ Rated @ 90 °C (194 °F) insulation maximum
Isolation voltageInput module: 50V (continuous), Basic Insulation Type, Inputs/Outputs to Backplane. Type tested for 60s @ 720V DC, Inputs/Outputs to Backplane
RedundancyNo
Short-circuit protection, outputs availableNo
Bus current draw60 mA @ 3.3V DC
Width31.5 mm
Height62 mm
Depth20 mm
ShockIEC 60068-2-27 (Test Ea, unpackaged shock): 25 g, nonoperating, 35 g (Panel Mount) nonoperating
VibrationIEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz
Terminal screw torque0.22...0.25 Nm (1.95...2.21 lb-in) (using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Surrounding air temperature, max65 °C
North American temperature codeT4
EmissionsCISPR 11 (IEC 61000-6-4): Class A
ESD immunityIEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges
Relative humidityIEC 60068-2-30 (Test Db, unpackaged damp heat), 5...95% noncondensing
Conducted RF immunityIEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunityIEC 61000-4-4: ±2 kV @ 5 kHz on signal ports
Operating temperature-20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock)
Surge transient immunityIEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports
Nonoperating temperature-40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Radiated RF immunityIEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz,
On-state voltage drop, max0.5V DC
Reverse polarity protectionNone
Output on-state current0.5 A
Number of outputs16 (1 physical output, 15 virtual)
Enclosure type ratingMeets IP20
Output voltage range5...30V DC
Off-state voltage, max1.0V DC
On-state current, min2 mA
Number of inputs1 Quadrature (ABZ) differential input
Pulse width, min2 μs
Input impedance, nom3580 Ohm
Input frequency, max250 kHz (50% duty)
Maximum count48 Bit
Phase separation, min500 ns
Input current range2 mA
Input voltage range0...30V DC
Off-state leakage current0.5 mA
ON-state voltage range2.6...30V DC