Industrial Automation
QUINT4-PS/12-24DC/24DC/2.5/SC - DC/DC converter


Input data | Nominal input voltage range: 12 VÃDC ... 24 VÃDC Input voltage range: 12 VÃDC ... 24 VÃDC -25Ã%Ã...Ã+33Ã% (SELV) Wide-range input: yes Electric strength, max.: 35 VÃDC (60 s) Inrush current: typ. 8.6 A Inrush current integral (I2t): typ. 0.1 A2s Inrush current limitation: 8.6 A Mains buffering time: typ. 16 ms (24ÃVÃDC) Current consumption: typ. 7.2 A (12ÃVÃDC) typ. 3.5 A (24ÃVÃDC) Switch-on time: < 1 s Input fuse: 15 A (fast blow, internal) Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
Output data | Efficiency: typ. 92.1 % (24ÃVÃDC) Output characteristic: U/I Advanced Smart HICCUP FUSE MODE Nominal output voltage: 24 VÃDC Setting range of the output voltage (USet): 24 VÃDC ... 28 VÃDC (> 24ÃVÃDC, constant capacity) Nominal output current (IN): 2.5 A Static Boost (IStat.Boost): 3.125 A (ââ°¤Ã40ðC) Dynamic Boost (IDyn.Boost): 5 A (ââ°¤Ã60ðCÃ(4.9Ãs)) Short-circuit-proof: yes No-load proof: yes Derating: > 60°C (2.5%/K of POut nom.) Output power (PN): 60 W Output power (PStat. Boost): 75 W Output power (PDyn. Boost): 120 W Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 32 VÃDC Residual ripple: < 20 mVPP Control deviation: < 1 % (change in load, static 10 % ... 90 %) Rise time: < 1 s (UOUT (10 % ... 90 %)) Connection in series: yes Maximum no-load power dissipation: < 1.3 W Power loss nominal load max.: < 8 W Connection in parallel: yes, for redundancy and increased capacity Signal (configurable) Digital: 0 VÃDC 24 VÃDC 22 mA Default: 24 VÃDC 22 mA 24ÃVÃDC for UOut >Ã0.9ÃxÃUSet |
Connection data | Input Position: 1.x Conductor connection Connection method: Screw connection rigid: 0.75 mm² ... 2.5 mm² flexible: 0.75 mm² ... 2.5 mm² flexible with ferrule without plastic sleeve: 0.75 mm² ... 2.5 mm² flexible with ferrule with plastic sleeve: 0.75 mm² ... 2.5 mm² rigid (AWG): 18 ... 14 Stripping length: 8 mm Tightening torque: 0.5 Nm ... 0.6 Nm Drive form screw head: Slotted L Output Position: 2.x Conductor connectionââ¬Ã¢¹ Connection method: Screw connection rigid: 0.5 mm² ... 2.5 mm² flexible: 0.5 mm² ... 2.5 mm² flexible with ferrule without plastic sleeve: 0.5 mm² ... 2.5 mm² flexible with ferrule with plastic sleeve: 0.5 mm² ... 2.5 mm² rigid (AWG): 20 ... 14 Stripping length: 8 mm Tightening torque: 0.5 Nm ... 0.6 Nm Drive form screw head: Slotted L Signal Position: 3.x Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Screw connection rigid: 0.14 mm² ... 2.5 mm² flexible: 0.14 mm² ... 2.5 mm² flexible with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm² flexible with ferrule with plastic sleeve: 0.25 mm² ... 2.5 mm² rigid (AWG): 26 ... 14 Stripping length: 8 mm Tightening torque: 0.5 Nm ... 0.6 Nm Drive form screw head: Slotted L |
Signaling | LED signaling Signal threshold: > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting) > 0.9ÃxÃUSet (LED lights up green) < 0.9ÃxÃUSet (LED flashes green) |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 2.6 kV DC (type test) 1.2 kV DC (routine test) Switching frequency: 130 kHz ... 130 kHz (Auxiliary converter stage) 70 kHz ... 250 kHz (Main converter stage) |
Product properties | Product type: DC/DC converters Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 1999348 h (25ðC) > 1120490 h (40ðC) > 471066 h (60ðC) Insulation characteristics Protection class: II Degree of pollution: 2 Life expectancy (electrolytic capacitors) Current: 1.25 A Temperature: 40°C Time: 242000 h Additional text: 24ÃVÃDC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹ Current: 2.5 A Temperature: 40°C Time: 160000 h Additional text: 24ÃVÃDC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 2.5 A Temperature: 30°C Time: 320000 h Additional text: 24ÃVÃDC |
Dimensions | Item dimensions Width: 32 mm Height: 99 mm Depth: 90 mm Item dimensions with alternative mounting Width: 90 mm Height: 99 mm Depth: 32 mm Installation dimensions Installation distance right/left (active): 15 mm / 15 mm (POutÃââ°¥50%Ã) Installation distance right/left (passive): 5 mm / 5 mm (POutÃââ°¥50%Ã) Installation distance right/left (active, passive): 0 mm / 0 mm (POutÃââ°¤50Ã%) Installation distance top/bottom (active): 30 mm / 30 mm (POutÃââ°¥50%Ã) Installation distance top/bottom (passive): 30 mm / 30 mm (POutÃââ°¥50%Ã) Installation distance top/bottom (active, passive): 30 mm / 30 mm (POutÃââ°¤50Ã%) |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: PN ââ°¥50%, 5Ãmm horizontally, 15Ãmm next to active components, 50Ãmm vertically alignable: PN <50%, 0Ãmm horizontally, 40Ãmm vertically top, 20 mm vertically bottom With protective coating: No |
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Plastic Type of housing: Polycarbonate (PC), ULÃ94ÃV0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (> 2000 m, observe derating) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15ÃHz, ñ2.5Ãmm amplitude; 15ÃHz ... 100ÃHz: 2.3Ãg 90ÃMin. (in accordance with IEC 60068-2-6) |
Standards and regulations | Overvoltage category EN 61010-1: IIÃ(ââ°¤Ã5000Ãm) Safety for measurement, control, and laboratory equipment Standard designation: Electrical safety (of control and regulation devices) Standards/specifications: IEC 61010-1 Protective extra-low voltage Standard designation: Protective extra-low voltage Standards/specifications: IEC 61010-1 (SELV) Mains voltage dips Standard designation: Mains variation/undervoltage Standards/specifications: ENÃ61000-4-29 |
Approvals | SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201) UL approvals: UL Listed ULÃ61010-1 UL Listed ULÃ61010-2-201 ANSI/ULÃ121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) UL Identification: ULÃListedÃULÃ61010-1 ULââ¬Ã¢¹ Identification: CAN/CSAÃC22.2 No.Ã61010-1-12 ULââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Identification: ULÃListedÃULÃ61010-2-201 ULââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Identification: CAN/CSAÃC22.2ÃNo.Ã61010-2-201:18 ULââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Identification: ULÃ121201 & CSAÃC22.2ÃNo.Ã213-17ÃClass I, Division 2, Groups A, B, C, D T4 (Hazardous Location) CB scheme Identification: IEC 61010-1 CB schemeââ¬Ã¢¹ Identification: IEC 61010-2-201 Shipbuilding Identification: DNV GL |
EMC data | EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU EMC requirements, power plant: ENÃ61850-3 ENÃ61000-6-5 Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) ENÃ55016 ENÃ61000-6-3 (Class B) DNVÃGL conducted interference: ClassÃB Additional text: Bridge and deck area DNVÃGL noise radiation: ClassÃB Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 4) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 2 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 4 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion B Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 1 kV (Test Level 4 - symmetrical) 2 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 4 - symmetrical) 2 kV (Test Level 4 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Power frequency magnetic field Standards/regulations: ENÃ61000-4-8 Frequency: 16.67 Hz 50 Hz 60 Hz 50 Hz 60 Hz 0 Hz Test field strength: 100 A/m 1 kA/m 300 A/m Additional text: 60 s 3 s DC, 60Ãs Comments: Criterion A Frequency range: 50 Hz ... 60 Hz Voltage dips Standards/regulations: ENÃ61000-4-29 Voltage: 24 VÃDC Voltage dip: 70 % 40 % 0 % Number of periods: 0.5 / 1 / 25 periods 5 / 10 / 50 periods 0.5 / 1 / 5 / 50 periods Time: 100 ms 50 ms Additional text: Test Level 2 Comments: Criterion A Criterion B Pulse-shape magnetic field Standards/regulations: ENÃ61000-4-9 Test field strength: 1000 A/m Comments: Criterion A Asymmetrical conducted disturbance variables Standards/regulations: ENÃ61000-4-16 Test level 1: 15 Hz 150 Hz (Test Level 3) Voltage: 10 V 1 V (Permanent) 1 V 1 V 10 V 10 V 10 V (Permanent) 100 V (1 s) Test level 2: 150 Hz 1.5 kHz (Test Level 3) Test level 3: 1.5 kHz 15 kHz (Test Level 3) Test level 4: 15 kHz 150 kHz (Test Level 3) Test level 5: 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) Test level 6: 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3) Comments: Criterion A Alternating component of direct voltage Standards/regulations: ENÃ61000-4-17 Alternating component: 10 % (UN) Frequency: 50 Hz 100 Hz 150 Hz 300 Hz Comments: Criterion A Attenuated oscillating wave Standards/regulations: ENÃ61000-4-18 Input, output (test levelÃ1): 1 MHz (Test Level 2 - symmetrical) Voltage: 0.5 kV 1 kV 0.5 kV 1 kV Input, output (test levelÃ2): 1 MHz (Test Level 2 - asymmetrical) Signals (test levelÃ1): 1 MHz (Test Level 2 - symmetrical) Signals (test levelÃ2): 1 MHz (Test Level 2 - asymmetrical) Comments: Criterion A Attenuated oscillating magnetic field Standards/regulations: ENÃ61000-4-10 Test field strength: 100 A/m Test level 1: 100 kHz Test level 2: 1 MHz Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |