Industrial Automation



| Type of voltage (input voltage) | DC |
| Type of output voltage | DC |
| Analogue input, current | No |
| Analogue input, voltage | No |
| Analogue output, current | No |
| Analogue output, voltage | No |
| Short-circuit protection, digital outputs available | Yes |
| Voltage type of supply voltage | DC |
| Type of digital output | Transistor |
| Insulation stripping length | 5069-RTB18-SPRING connections: 10 mm (0.39 in.) |
| Suitable for safety functions | No |
| Time delay at signal exchange | 20 ms |
| Analogue input, resistor | No |
| Analogue input, resistor temperature | No |
| Analogue input, thermocouple | No |
| Analogue input signal configurable | No |
| Analogue output signal configurable | No |
| Digital in-/outputs, configurable | Yes |
| Type of electric connection | Screw-/spring clamp connection |
| Input current, max | 8 mA |
| Power dissipation, max | 3 W |
| Off-state current, max | 1 mA |
| On-state current, min | 4 mA |
| Off-state voltage, max | 1.5 V |
| Pulse width, min | 125 ns |
| Pulse separation, min | 100 ns |
| Output short circuit/overload protection | Yes |
| Thermal dissipation, max | 10.2 BTU/h |
| Reverse voltage protection | 32V DC |
| On-state voltage, nom | 24V DC |
| On-state voltage drop, max | <0.3V DC |
| ON-state voltage | 3...32V DC |
| Output voltage range | 10...32V DC |
| Voltage category | 12/24V DC source |
| Overvoltage protection, max | 36V (fuse protected) |
| No load detection diagnostics | Yes (per channel diagnostics) |
| Output short circuit/overload/overtemp detection | Yes (per channel diagnostics) |
| On-state output current, min | 1 mA per channel 4 mA per module |
| Output control in fault state per point | Hold last state, On, Off (default) |
| Output states in program mode per point | Hold last state, On, Off (default) |
| Output states in fault mode per point | Hold last state, On, Off (default) |
| Outputs | 4 Channels (1 group of 4), sourcing |
| Inputs | 2 quadrature (ABZ) differential inputs |
| Duration of fault mode per point | 1 s, 2 s, 5 s, 10 s, Forever (default) |
| Module keying | Electronic keying via programming software |
| Pilot duty | Yes (make current electronically limited/protected @ 3.6 A) |
| Indicators | 1 green/red module status indicator, 10 yellow/red I/O status indicator |
| Wiring category | 2 - on shielded output ports, 2 - on output power ports, 2 - on shielded counter ports |
| Isolation voltage | 250V (continuous), basic insulation type, No isolation between SA power and I/O ports, No isolation between individual I/O ports, Type tested at 1500V AC for 60 s |
| Wire size | 5069-RTB18-SPRING connections: 0.5...1.5 mmò (22...16 AWG) solid or stranded shielded copper wire rated at 105 ðC (221 ðF), or greater, 2.9 mm (0.11 in.), maximum diameter including insulation 5069-RTB18-SCREW connections: 0.5â⬦1.5 mmò (22â⬦16 AWG) solid or |
| Width | 22 mm |
| Height | 144.57 mm |
| Depth | 105.42 mm |
| Enclosure type | None (open-style) |
| Slot width | 1 |
| Weight, approx | 175 g |
| RTB keying | None |
| Vibration | 5 G @ 10...500 Hz |
| Shock | Operating: 30 G, Non operating: 50 G |
| RTB torque | 5069-RTB18-SCREW RTB only: 0.4 Nm (3.5 lbin) |
| DIN rail | Compatible zinc-plated chromate-passivated steel DIN rail |
| Surrounding air temperature, max | 60 ðC |
| Operating temperature | 0 ðC |
| Nonoperating temperature | -40 ðC |
| Emissions | IEC 61000-6-4 |
| Relative humidity | 5...95% noncondensing |
| Voltage variation | 10 ms interruption on MOD Power port |
| ESD immunity | 6 kV contact discharges, 8 kV air discharges |
| Conducted RF immunity | 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz |
| EFT/B immunity | ñ4 kV @ 5 kHz on power ports, ñ2 kV @ 5 kHz on shielded output ports, ñ2 kV @ 5 kHz on shielded counter ports |
| Surge transient immunity | ñ1 kV line-line (DM) and ñ2 kV line-earth (CM) on power ports, ñ2 kV line-earth (CM) on shielded output ports, ñ2 kV line-earth (CM) on shielded counter ports |
| Radiated RF immunity | 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz |
| North American temperature code | T4 |
| ATEX temp code | T4 |
| IECEx temp code | T4 |
| SA power | 3 A @ 18...32V DC |
| Counter input ratings | 4 mA @ 3...32V DC |
| MOD power | 50 mA @ 18...32V DC |
| MOD Power passthrough | 9.55 A @ 18...32V DC |
| SA Power passthrough | 9.95 A @ 10...32V DC |