| SIL according to IEC 61508 | 2 |
| Safety integrity level claim limit | 2 |
| Hardware fault tolerance | 1 |
| Safe failure fraction | 98.95 % |
| PFH | 7.19E-9 |
| PFD | 4.13E-09 |
| Mode of operation | High demand mode |
| With approval according to UL | Yes |
| With approval for TUV | Yes |
| Performance level according to EN ISO 13849-1 | Level d |
| Mission time | 20 Year |
| Hours of operation | 24 h |
| MTTFd | 378 |
| Days of operation | 365 Days |
| DC avg. (EN ISO 13849-1) | 97.66 % |
| Category | Up to 3 |
| Performance level | Up to d |
| T cycle | 8/28.8 (h/s) |
| Rated operating frequency | 4 kHz |
| Evaluation inputs | One- and two-channel |
| Type of electric connection | Screw connection |
| Power consumption | 2 W |
| Rated control supply voltage Us at DC | 24 V |
| Wire size | 0.2...2.5 mmò (24...14 AWG) |
| Number of outputs, safety related, undelayed, with contact | 0 |
| Number of outputs, safety related, delayed, with contact | 0 |
| Number of outputs, signalling function, undelayed, with contact | 0 |
| Number of outputs, signalling function, delayed, with contact | 0 |
| Number of outputs, signalling function, undelayed, semiconductors | 1 |
| Number of outputs, signalling function, delayed, semiconductors | 0 |
| Voltage type for actuating | DC |
| Suitable for safety functions | Yes |
| With detachable clamps | Yes |
| With feedback circuit | Yes |
| Surge auxillary output current duration, max | 5 ms |
| Surge safety output current duration, max | 5 ms |
| Continuous auxiliary output current | 50 mA |
| Surge auxiliary output current | 700 mA |
| Aggregate current of outputs per module, max | 1.8 A |
| Continuous safety output current, max | 0.5 A |
| Surge safety output current, max | 1.5 A |
| Number of outputs, safety related, undelayed, semiconductor | 2/4 |
| Number of outputs, safety related, delayed, semiconductor | 0/2 |
| Other output | SWS output |
| Operating voltage range | 20.4 V |
| Configurable logic | Logic setting 1 - cat 1 stop, logic IN off, Logic setting 2 - cat 1 stop with logic IN, Logic setting 3 - safe limited slow speed, logic IN off, Logic setting 4 - safe limited slow speed with logic IN, Logic setting 5...8 - guard locking with delayed unlo |
| Operating temperature | -5 ðC |
| Enclosure protection | IP40 (NEMA 1) |
| Relative humidity | 90% |
| Height | 119.4 mm |
| Width | 22.5 mm |
| Depth | 113.6 mm |
| Vibration | 10...55 Hz, 0.35 mm |
| Shock | Shock proof, operating: 10 G, 16 ms |
| Function rotational speed monitoring | Yes |
| Function standstill monitoring | Yes |