ROCKWELL AUTOMATION 2080-IQ4
ROCKWELL AUTOMATION 2080-IQ4
ROCKWELL AUTOMATION 2080-IQ4
ROCKWELL AUTOMATIONAvailable

Micro800 4 Point IEC Digital Input

2080 Micro800 System, 4-ch Digital Input module
Product Code: 2080-IQ4
Partner cod.: 2080-IQ4
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Tecnichal data
Number of digital inputs4
Digital inputs configurableNo
Digital outputs configurableNo
Type of voltage (input voltage)AC/DC
Type of output voltageDC
Type of digital outputTransistor
Type of electric connectionScrew connection
Status indicator4 yellow
ON-state current, max5 mA
On-state current, nom3.0 mA @ 24V DC
Wire size0.2... 2.5 mm2 (24...12 AWG) solid or stranded copper wire rated @ 90 °C (194 °F), or greater, insulation maximum
Isolation voltage50V (continuous), basic insulation type, inputs to backplane type tested for 60 s @ 720V DC, inputs to backplane
RedundancyNo
SIL according to IEC 61508None
Surrounding air temperature, max65 °C
North American temperature codeT4
Relative humidity5...95% noncondensing
Operating temperature-20 to 65 °C
Nonoperating temperature40 to 85 °C
Off-state current, max1.5 mA
ON-state voltage, max30V DC, 30V AC (rms)
Off-state voltage, max5V DC, 3.5V AC (rms)
On-state voltage, min9.0V DC, 10.25V AC (rms)
On-state current, min2.0 mA @ 9V DC, 2.0 mA @ 9V AC (rms)
IEC input compatibilityType 3
Input filter timeON to OFF: 8...10 ms AC/DC
Input impedance0...3V, >4 KΩ, 3...12V, 3.5 KΩ minimum, 12...30V, >4 KΩ <10 KΩ
Terminal base screw torque, max0.22...0.25 Nm (1.95...2.21 lb-in) (using a 2.5 mm (0.10 in.) flat-blade screwdriver)
ShockOperating: 25 g
Vibration2.0 G @ 10…500 Hz
Mounting torque0.2 Nm
Explosion safety category for gasNone
Explosion safety category for dustNone