Industrial Automation




| Nominal value output voltage 1 | 24 V |
| Secondary voltage adjustable | Yes |
| Max. output current 1 | 10 A |
| Nominal value output current 1 | 10 A |
| Power output | 240 W |
| Voltage type of supply voltage | AC/DC |
| 1st secondary output voltage | 24 V |
| Rated supply voltage at AC 50 Hz | 100 V |
| Rated supply voltage at AC 60 Hz | 100 V |
| Rated supply voltage at DC | 110 V |
| Power reserves | 20 % |
| Derating | 6 W/ðC |
| DC OK relay contact | Yes |
| Input inrush current limiter | Active |
| Adjustment range | 24 V |
| Power factor | 0.97 typical |
| Operational range | 90â⬦132V AC |
| Rated output current | 8.6 A, 28V |
| External input fuse, min | B-6 A or C-6 A |
| Power losses | 12.1 W typical |
| Sub group | Essential line |
| Hold-up time | >46 ms @ 120V |
| Efficiency | 95.2% typical |
| Input inrush current | 6 A/9 A |
| Special family function | Dynamic 120% power boost under 45C Degree |
| Rated input current | 5 A, 100V AC |
| Output voltage stabilized | Yes |
| Rail mounting possible | Yes |
| Stabilized | Yes |
| Height | 124 mm |
| Depth | 117 mm |
| Direct mounting possible | No |
| Width | 39 mm |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Screw connection |
| Shock | 30 G, 6ms 20 G, 11ms |
| MTBF | 661 kh (40 ðC, SN29500) |
| Wall mounting possible | Yes |
| Vibration | 2 G |
| Ripple and noise, max | 50 mV |
| Operating temperature | -25 ðC |
| Storage temperature | -25 ðC |
| Lifetime, min | 120 kh (+40 ðC) |
| Relative humidity | 5 to 95 % |
| Weight | 600 g |
Description other products