Smart Motor Controller, 480A, 600V, 3-Phase, 50/60Hz, 100...240V AC, Open







| With display | No | 
| Voltage type for actuating | AC/DC | 
| Rated operating voltage Ue | 200 V | 
| Rated control supply voltage at AC 50 Hz | 100 V | 
| Rated control supply voltage at AC 60 Hz | 100 V | 
| Fan power rating | 60 VA | 
| Overload current | 160 A | 
| Controller type | SMC-3 | 
| DV/DT protection | 1000V/õs for power circuit | 
| Repetitive peak voltage | 1600V per UL/CSA/NEMA for power circuit | 
| Operating frequency | 50/60 Hz per UL/CSA/NEMA for power circuit | 
| Line connected motor power, max | 250...500 Hp @ 575V AC, 60 Hz, 3-phase | 
| Delta connected motor power, max | 560 kW @ 500V AC, 50 Hz, 3-phase | 
| Overvoltage category | III per IEC for side mount auxiliary contacts | 
| Rated impulse voltage | 6 kV for power circuit | 
| Dielectric withstand | 2500V AC per IEC for power circuit | 
| Line connected motor current | 160...480 A @ 500/575V AC, 3-phase | 
| Delta connected motor current | 277...831 A @ 500/575V AC, 3-phase | 
| Insulation voltage | Rated 600V AC per UL/CSA/NEMA for power circuit | 
| Rated operational voltage | 250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts | 
| Rated control power during start with fan | 200 mA @ 120V AC/120 mA @ 240V AC, 600 mA @ 24V AC/DC | 
| Input OFF-state current | <10 mA, <12 mA @ input off-state voltage (IN1, IN2) for control circuit | 
| Short-circuit protection device list | Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L | 
| Number of contacts | TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts | 
| High capacity available fault current, max | 69 kA @ 600V, maximum current 800 A time delay Class J or Class L fuse for line connected motors | 
| Type of current | TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts | 
| Conventional thermal current (Ith) | TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts | 
| Type of control circuit | TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts | 
| Type of contacts | TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts | 
| Utilization category | TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts | 
| Rated operational current, max | TB-97, -98 (OVLD/Fault): 0.6 A @ 120V AC and 0.3 A @ 240V AC for auxiliary contacts | 
| Standard controller feature | Soft stop | 
| Standard available fault current, max | 42 kA @ maximum standard fuse 1600 A for delta device operational current rating | 
| Integrated motor overload protection | Yes | 
| Short circuit protection device performance (SCPD) type | Type 1 | 
| Selectable overload trip class | Trip Class 10, 15, or 20 | 
| Selectable start times | 2, 5, 10, 15, 20, 25, or 30 s | 
| Input OFF-state voltage (IN1, IN2), max | 40V AC, 17V DC/12V AC for control circuit | 
| Selectable current limit | 150%, 250%, 350%, and 450% of full load current | 
| Input ON-state voltage, during start (IN1, IN2) | 85V AC, 19.2V DC/19.2V AC minimum for control circuit | 
| Input ON-state current (IN1, IN2) | 9.8 mA @ 120V AC/19.6 mA @ 240V AC for control circuit, 7.3 mA @ 24V AC/DC for control circuit | 
| Degree of protection (IP) | IP2X | 
| Weight | 45.8 kg | 
| Shock | Operational: 15 G | 
| Width | 290 mm (11.42 inch) | 
| Depth | 298 mm (11.73 inch) | 
| Height | 600 mm (23.62 inch) | 
| Cable size | 0.2...2.5 mm2 (24...14 AWG) for control terminals | 
| Vibration | Operational: 1.0 G peak, 0.15 mm (0.006 inch) displacement | 
| Make | TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts | 
| Break | TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts | 
| Tightening torque | 0.45...0.9 Nm (4.0...8.0 lb.inch) for control terminals | 
| Internal bypass | Yes | 
| Function | Single direction | 
| Selectable kick start - 450% FLA | 0, 0.5, 1.0, or 1.5 s | 
| Selectable initial torque | 15%, 25%, 35%, and 65% of locked rotor torque | 
| Selectable soft stop | Off, 100%, 200%, or 300% of the start time setting when wired | 
| Steady state heat dissipation | 239 W | 
| Storage and transportation temperature | -25 ðC | 
| Rated surrounding temperature range without derating | -5 ðC | 
| Humidity | 5...95% noncondensing | 
| Operating temperature | Open: -5 to 50 ðC (23 to 122 ðF) | 
| EMC emission levels | Radiated emission: Class A per IEC | 
| EMC immunity levels | Surge transient: per EN/IEC 60947-4-2 per IEC | 
| Altitude | 2000 m | 
| Pollution degree | 2 | 
| Mounting hole size | 11.5 mm | 
| Number of poles | Equipment is designed for 3-phase only for power circuit | 
| Power pole holes | Two M12 x 1.75 diameter holes per power pole for load power terminals | 
| Enclosure | Open type | 