Industrial Automation
SC 2,5-NS/ 1-L GNYE - COMBI coupling






| Product properties | Product type: Terminal coupling Area of application: Railway industry Machine building Plant engineering Number of positions: 1 Pitch: 5.2 mm Number of connections: 1 Number of rows: 1 Potentials: 1 Data management status Article revision: 03 Insulation characteristics Overvoltage category: III Degree of pollution: 3 | 
| Electrical properties | Rated surge voltage: 6 kV Maximum power dissipation for nominal condition: 0.77 W | 
| Connection data | Nominal cross section: 2.5 mm² Stripping length: 10 mm Internal cylindrical gage: A3 Connection in acc. with standard: IEC 61984 Conductor cross section rigid: 0.08 mm² ... 4 mm² Cross section AWG: 28 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.08 mm² ... 2.5 mm² Conductor cross section, flexible [AWG]: 28 ... 14 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.14 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.14 mm² ... 2.5 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² Nominal current: 24 A Maximum load current: 24 A (with 4 mm² conductor cross section) Nominal voltage: 500 V | 
| Dimensions | Width: 5.2 mm End cover width: 2.2 mm Height: 43.5 mm Depth on NS 15: 34 mm Depth on NS 35/7,5: 34 mm Depth on NS 35/15: 41.5 mm Pitch: 5.2 mm | 
| Material specifications | Color: green-yellow Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60 °C Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 130 °C Relative insulation material temperature index (Elec., UL 746 B): 130 °C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Calorimetric heat release NFPA 130 (ASTM E 1354): 28 MJ/kg Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed | 
| Electrical tests | Surge voltage test Test voltage setpoint: 7.3 kV Result: Test passed Short-time withstand current 2.5 mm²: 0.3 kA Power-frequency withstand voltage Test voltage setpoint: 1.89 kV Result: Test passed | 
| Mechanical properties | Mechanical data Open side panel: Yes | 
| Mechanical tests | Attachment on the carrier DIN rail/fixing support: NS 35 Test force setpoint: 1 N Result: Test passed | 
| Environmental and real-life conditions | Needle-flame test Time of exposure: 30 s Result: Test passed Oscillation/broadband noise Specification: DIN EN 50155 (VDE 0115-200):2008-03 Spectrum: Service life test category 1, class B, body mounted Frequency: f1 = 5 Hz to f2 = 150 Hz ASD level: 0.964 (m/s²)²/Hz Acceleration: 0.58g Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Specification: DIN EN 50155 (VDE 0115-200):2008-03 Pulse shape: Half-sine Acceleration: 5g Shock duration: 30 ms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) Result: Test passed Ambient conditions Ambient temperature (operation): -60 °C (max. operating temperature see derating curve) Ambient temperature (storage/transport): -25 °C ... 60 °C (for a short time, no longer than 24 h, -60 °C to +70 °C) Ambient temperature (assembly): -5 °C ... 70 °C Ambient temperature (actuation): -5 °C ... 70 °C Permissible humidity (operation): 20 % ... 90 % Permissible humidity (storage/transport): 30 % ... 70 % | 
| Standards and regulations | Connection in acc. with standard: IEC 61984 | 
| Mounting | Mounting type: NS 35/7,5 NS 35/15 Assembly note: Use of a parallel pressing tool is recommended for easy latching of the COMBI connector and coupling elements for self-assembly | 