TTC-6-2X1-24DC-UT - Surge protection device

Surge protection for two signal wires with common reference potential, e.g., Digital IN/OUT.
Product Code: 2906799
Partner cod.: 2906799
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Product propertiesIEC test classification: C1
C2
C3
D1
Type: DIN rail module, one-piece
Product type: Surge protection for MCR technology
Product family: TERMITRAB complete
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal voltage UN: 24 VÂDC
Connection dataConnection method: Screw connection
Screw thread: M3
Tightening torque: 0.5 Nm ... 0.6 Nm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e2773f659b7fc7488928febdcf8a1242/-S204x204-FJPG
Width: 6.2 mm +0.1Âmm
Height: 105.8 mm
Depth: 69.5 mm (incl. DIN rail 7.5Âmm)
Material specificationsFlammability rating according to UL 94: V-0
Insulating material: PBT
Housing material: PBT
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitDirection of action: Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC: 30 VÂDC
21 VÂAC
Rated current: 600 mA (40°C)
Operating effective current IC at UC: ≤ 5 µA
Residual current IPE: ≤ 10 µA
Nominal discharge current In (8/20) µs (line-ground): 5 kA
Pulse discharge current Iimp (10/350)µs (line-earth): 0.5 kA
Total discharge current Itotal (8/20)µs: 10 kA
Voltage protection level Up (line-earth): ≤ 140 V (C1 - 1ÂkV / 500ÂA)
≤ 130 V (C2 - 10 kV / 5 kA)
≤ 45 V (C3 - 25ÂA)
≤ 50 V (C3 - 100ÂA)
Voltage protection level Up static (line-earth): ≤ 55 V (C1 - 1ÂkV / 500ÂA)
≤ 80 V (C2 - 10 kV / 5 kA)
Response time tA (line-earth): ≤ 1 ns
Input attenuation aE, asym.: typ. 0.3 dB (≤ 270 kHz/150 Ω)
typ. 0.3 dB (≤ 407 kHz / 100 Ω)
Cut-off frequency fg (3ÂdB), asym. (PE) in 100ÂΩ system: typ. 1280 kHz
Cut-off frequency fg (3ÂdB), asym. (PE) in 150ÂΩ system: typ. 960 kHz
Capacity (Core-Earth): typ. 2.2 nF
Resistance per path: 1.65 Ω ±20Â%
Surge protection fault message: none
Max. required back-up fuse: 630 mA (FF)
Impulse durability (line-earth): C1 - 1ÂkV / 500ÂA
C2 - 10ÂkV / 5ÂkA
C3 - 100ÂA
D1 - 500ÂA
Pulse reset time (line-earth): ≤ 300Âms
Additional technical data
Max. total discharge current I total max (8/20)µs: 20 kA (1x)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 85°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 4000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
ApprovalsConformity/Approvals
UL, USA / Canada: Class I, Div. 2, Groups A, B, C, D T4
Standards and regulationsStandards/specifications: IEC 61643-21
Note: 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specifications: ENÂ61643-21
Note: 2001 + A1:2009 + A2:2013
MountingMounting type: DIN rail: TH 35 - 7.5 mm
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00233.pdf

Approvals_00062.pdf

Approvals_00217.pdf

Approvals_00218.pdf

Approvals_00552.pdf

Approvals_00559.pdf

Approvals_00975.pdf

Approvals_01844.pdf

Certification_00159.pdf

Certification_00201.pdf

Certification_00202.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_01018.pdf

Manufacturer_declaration_02339.pdf

Manufacturer_declaration_16172.pdf

Product_information_00033.pdf

Product_information_00693.pdf

Product_information_01021.pdf

Technical_drawing_40330.pdf