Industrial Automation
PSR-SPP-230AC/ESAM2/3X1/1X2/B - Safety relays


Product properties | Product type: Safety relays Product family: PSRclassic Application: Emergency stop Safety door Mechanical service life: approx. 107 cycles Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/ENÃ61810-3 |
Electrical properties | Maximum power dissipation for nominal condition: 2.88 W Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VÃAC Rated surge voltage/insulation: 4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV between A1-A2/logic/enabling and signaling current paths) |
Input data | General Rated control circuit supply voltage US: 230 VÃAC -15Ã% / +10Ã% Rated control supply current IS: 22 mA Voltage at input/start and feedback circuit: ~ 24 VÃDC Typical response time: 50 ms (manual start) 300 ms (automatic start) Typ. starting time with Us: 300 ms (when controlled via A1 or S11/S12) Typical release time: 20 ms (when controlled via S11/S12) 150 ms (when controlled via A1) Recovery time: 1 s Maximum switching frequency: 0.5 Hz Protective circuit: Surge protection; Suppressor diode Surge protection; Varistor Max. permissible overall conductor resistance: 50 é |
Output data | Contact switching type: 3 enabling current paths 1 signaling current path Contact material: AgSnO2, gold-flashed Maximum switching voltage: 250 V AC/DC Minimum switching voltage: 10 V AC/DC Limiting continuous current: 6 A (Enabling current paths) 5 A (Signaling current path) Maximum inrush current: 6 A Inrush current, minimum: 10 mA Sq. Total current: 72 A2 Interrupting rating (ohmic load) max.: 144 W (at 24 V DC) 230 W (at 48 V DC) 68 W (at 110 V DC) 88 W (at 220 V DC) 2000 VA (for 250 V AC) Maximum interrupting rating (inductive load): 48 W (at 24 V DC) 40 W (at 48 V DC) 35 W (at 110 V DC) 33 W (at 220 V DC) Switching capacity min.: 100 mW Switching capacity (360/h cycles): 6 A (24ÃVÃDC) 5 A (230 V AC) Switching capacity (3600/h cycles): 3 A (24ÃV (DC13)) 3 A (230 V (AC 15)) Output fuse: 10 A gL/gG NEOZED (Enabling current paths) 6 A gL/gG NEOZED (Signaling current paths) |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross-section AWG: 24 ... 16 Stripping length: 8 mm |
Signaling | Status display: 2 x green LEDs Operating voltage display: 1 x green LED |
Dimensions | Width: 22.5 mm Height: 112 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENÃISOÃ13849 Category: 1 (up to Cat. 4 depending on the application) Performance level (PL): c (up to PLÃe depending on the application) Safety dataââ¬Ã¢¹ Safety Integrity Level (SIL): 1 (up to SILÃ3 depending on the application) Safety dataââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Safety Integrity Level (SIL): 1 (up to SILÃ3 depending on the application) Safety dataââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Safety Integrity Level (SIL): 1 (up to SILÃ3 depending on the application) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -25°C ... 55°C Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: ââ°¤ 2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10ÃHzÃ...Ã150ÃHz, 2g |
Approvals | Conformity/Approvals Conformance: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: IEC 60664-1 |
Mounting | Mounting type: DIN rail mounting Mounting position: any Connection method: Push-in connection |
Description other products