PT 4-EX(I)-BE - Surge protection base-element

Base element for protective plug PT with protective circuit for a 4-core floating EEx ia signal circuit. Nominal voltage: 24 V DC, for mounting on NS 35/7.5 and NS 35/15, housing width: 17.5 mm
Product Code: 2839486
Partner cod.: 2839486
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Product propertiesType: Base element, DIN rail mounting
Product type: Base element
Product family: PLUGTRAB PT
Number of positions: 4
Wire pairs per module: 2
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal voltage UN: 24 VÂDC
Connection dataConnection method: Screw connection
Screw thread: M3
Tightening torque: 0.5 Nm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
Ex dataMaximum inner capacitance Ci: 1.1 nF
Max. internal inductance Li: 1 µH
Max. input current Ii: 500 mA (T4 / ≤ 80°C)
500 mA (T5 / ≤ 55°C)
500 mA (T6 / ≤Â40°C)
Max. input voltage Ui: 30 VÂDC
max. input power Pi: 850 mW (T4 / ≤ 80°C)
700 mW (T5 / ≤ 55°C)
700 mW (T6 / ≤Â40°C)
Maximum inner time factor (Ri/Li): ≤ 10 µs
Ambient temperature (operation): -40°C ... 80°C (T4)
-40°C ... 55°C (T5)
-40°C ... 40°C (T6)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f8998b053f0d754d92907f440e2375f4/-S204x204-FJPG
Width: 17.7 mm
Height: 90 mm
Depth: 51.5 mm (incl. DIN rail 7.5Âmm)
Horizontal pitch: 1 Div.
Material specificationsColor: Copper
Flammability rating according to UL 94: V-0
Housing material: PA 6.6
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMaximum continuous voltage UC: 30 VÂDC
21 VÂAC
Rated current: 500 mA (40°C)
Resistance per path: 0 Ω
Surge protection fault message: none
Max. required back-up fuse: 500 mA (T)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 85°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m (amsl)
ApprovalsConformity/Approvals
ATEX: ïÃ‹œ II 1 G Ex ia IIC T4...T6
ïÃ‹œ II 1 D Ex iaD 20 IP6x T85°C...135°C
Standards and regulationsStandards/specifications: ENÂ61643-21
ENÂ60079-0
ENÂ60079-11
IEC 60079-0
IEC 60079-11
Note: A2:2013
2018
2012
2017
2011
MountingMounting type: DIN rail: 35 mm
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01653.pdf

Approvals_01705.pdf

Approvals_01801.pdf

Certification_00275.pdf

Certification_00294.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00575.pdf

Manufacturer_declaration_01993.pdf

Package_slip_00384.pdf

Technical_drawing_38755.pdf