PHOENIX CONTACT 2801262
PHOENIX CONTACT 2801262
PHOENIX CONTACTNot available

PT-IQ-2X2+F-12DC-PT - Surge protection device

Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for two 2-wire floating signal circuits. Indirect grounding via gas-filled surge arrester.
Product Code: 2801262
Partner cod.: 2801262
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
NotesGeneral
Note: Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Product propertiesIEC test classification: C1
C2
C3
D1
Type: DIN rail module, two-section, divisible
Product type: Surge protection for MCR technology
Product family: PLUGTRAB IQ
Surge protection fault message: Optical, multi-stage
Wire pairs per module: 2
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal voltage UN: 12 VÂDC
Connection dataConnection method: Push-in connection
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/fec67ec3dcbbe64eb7bc973ba4b86189/-S204x204-FJPG
Width: 17.7 mm
Height: 109.3 mm
Depth: 77.5 mm (incl. DIN rail 7.5Âmm)
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
Housing material: PA 6.6
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitDirection of action: Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC: 15 VÂDC
10 VÂAC
Rated current: 700 mA (50°C)
Operating effective current IC at UC: ≤ 1 µA (in the signal circuit)
Residual current IPE: ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line): 10 kA
Nominal discharge current In (8/20) µs (line-ground): 10 kA
Nominal discharge current In (8/20) µs (line-signal ground): 10 kA
Pulse discharge current Iimp (10/350)µs (line-earth): 2.5 kA
Pulse discharge current Iimp (10/350)µs (line-signalground): 2.5 kA
Total discharge current Itotal (8/20)µs: 20 kA
Voltage protection level Up (line-line): ≤ 65 V (C1 - 1ÂkV / 500ÂA)
≤ 95 V (C2 - 10 kV / 5 kA)
≤ 35 V (C3 - 25ÂA)
≤ 40 V (C3 - 50ÂA)
Voltage protection level Up (line-earth): ≤ 900 V (C1 - 1ÂkV / 500ÂA)
≤ 1300 V (C2 - 10 kV / 5 kA)
≤ 1000 V (C3 - 25ÂA)
≤ 1300 V (C3 - 100ÂA)
Voltage protection level Up (line-signalground): ≤ 600 V (C1 - 1ÂkV / 500ÂA)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25ÂA)
≤ 800 V (C3 - 100ÂA)
Voltage protection level Up static (line-line): ≤ 45 V (C1 - 1ÂkV / 500ÂA)
Response time tA (line-line): ≤ 1 ns
Response time tA (line-earth): ≤ 100 ns
Response time tA (line-signalground): ≤ 100 ns
Input attenuation aE, sym.: typ. 0.3 dB (≤ 95 kHz/150 Ω)
Cut-off frequency fg (3ÂdB), sym. in 150ÂΩ system: typ. 600 kHz
Capacity (Core-Core): typ. 4 nF
Resistance per path: 1.2 Ω ±5Â%
Surge protection fault message: Optical, multi-stage
Max. required back-up fuse: 800 mA (FF)
Impulse durability (line-line): C1 - 1ÂkV / 500ÂA
C2 - 10ÂkV / 5ÂkA
C2 - 10ÂkA
C3 - 50ÂA
Impulse durability (line-earth): C1 - 1ÂkV / 500ÂA
C2 - 10ÂkV / 5ÂkA
C2 - 10ÂkA
C3 - 100ÂA
D1 - 2.5ÂkA
Impulse durability (line-signalground): C1 - 1ÂkV / 500ÂA
C2 - 10ÂkV / 5ÂkA
C2 - 10ÂkA
C3 - 100 A
D1 - 2,5ÂkA
Pulse reset time (line-line): ≤ 25Âms
Pulse reset time (line-earth): ≤ 50Âms
Pulse reset time (line-signalground): ≤ 50Âms
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 4000 m (amsl)
Standards and regulationsStandards/specifications: IEC 61643-21
ENÂ61643-21
ENÂ61000-6-2
ENÂ61000-6-3
Note: 2000 + A1:2008, modified
2001 + A1:2009
2007 + A1:2011
2005
MountingMounting type: DIN rail: 35 mm
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00062.pdf

Approvals_01843.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00690.pdf

Manufacturer_declaration_02072.pdf

Manufacturer_declaration_15039.pdf

Package_slip_00397.pdf

Product_information_00033.pdf

Product_information_01016.pdf

Technical_drawing_38523.pdf