Industrial Automation
PSR-MM25-1NO-2DO-24DC-SP - Safety relay module


Product properties | Product type: Safety device Application: Zero-speed safety relay Times Typ. starting time with Us: < 1 s Response time: typ. 20 ms (at 50ÃHz input frequency) Delay time range: 0.5 s ... 20 s ñ1Ã% (K1, K2 can be parameterized) |
Electrical properties | Nominal operating mode: 100% operating factor Interfaces: Without sensor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VÃAC 400 VÃAC with isolation paths between (L1/L2/L3) and the remaining current paths 690 VÃAC (with isolation paths within L1/L2/L3) Rated surge voltage/insulation: Basic insulation 4ÃkV: between all current paths and housing Basic insulation 8ÃkV: between L1 and L2 between L1 and L3 between L2 and L3 Safe isolation, reinforced insulation 6ÃkV: between A1/A2 and 13/14 between MO/FO and 13/14 Safe isolation, reinforced insulation 8ÃkV: between L1/L2/L3 and A1/A2 between L1/L2/L3 and MO/FO between L1/L2/L3 and 13/14 Supply Rated control circuit supply voltage US: 20.4 VÃDC ... 26.4 VÃDC 24 VÃDC -15Ã% / +10Ã% Rated control supply current IS: typ. 50 mA Power consumption at US: typ. 1.2 W Inrush current: 5.6 A (ÃâtÃ=Ã400Ãõs at Us) Filter time: 1 ms (at A1 in the event of voltage dips at Us) Protective circuit: Surge protection; Suppressor diode Protection against polarity reversal for rated control circuit supply voltage |
Input data | Measurement Voltage input signal: max. 690 V AC/DC (at L1/L2/L3) Limit frequency: max. 3 kHz (At voltages >Ã2ÃVRMS) Current consumption: max. 0.35 mA (at L1/L2/L3) |
Output data | Relay: Enabling current path Output description: safety-related N/O contacts Number of outputs: 1 (undelayed) Contact switching type: 1 enabling current path Contact material: AgSnO2 Switching voltage: min. 24 V AC/DC max. 250 V AC/DC (Observe the load curve) Switching capacity: min. 72 mW Inrush current: min. 3 mA max. 5 A Limiting continuous current: 5 A (observe derating) Sq. Total current: 25 A2 (observe derating) Switching frequency: max. 0.5 Hz Mechanical service life: 10x 106 cycles Output fuse: 5 A gL/gG Signal Number of outputs: 2 (digital, PNP) Voltage: 23 VÃDC (US - 1 V) Current: max. 100 mA Maximum inrush current: 500 mA Short-circuit protection: Yes |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross-section AWG: 24 ... 16 Stripping length: 8 mm |
Signaling | Status display: 4 x LED Bi-Colour |
Dimensions | Width: 12.5 mm Height: 116.6 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENÃISOÃ13849 Category: 3 Performance level (PL): e (4ÃAÃDC13; 5ÃAÃAC15; 17520Ãswitching cycles/year) Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 3 (4ÃAÃDC13; 5ÃAÃAC15; 17520Ãswitching cycles/year) Safety data: ENÃIEC 62061 Safety Integrity Level (SIL): 3 (4ÃAÃDC13; 5ÃAÃAC15; 17520Ãswitching cycles/year) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -20°C ... 55°C (observe derating) Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: max. 2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10ÃHzÃ...Ã150ÃHz, 2g |
Approvals | CE Certificate: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: DINÃENÃ50178 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: See derating curve Mounting position: vertical or horizontal Connection method: Push-in connection |