Industrial Automation
AXC 1050 - Controller


Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Type: modular Product type: Controller Product family: Axiocontrol Insulation characteristics Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) Display Diagnostics display: No |
System properties | Processor: Altera Nios II 1x 100 MHz Retentive data storage: 48 kByte (NVRAM) IEC 61131 runtime system Program memory: 2 Mbyte Data storage system: 2 Mbyte Number of control tasks: 8 Axioline Amount of process data: max. 8192 bit (per station) max. 4096 bit (AxiolineÃF local bus (input)) max. 4096 bit (AxiolineÃF local bus (output)) Number of supported devices: max. 63 (per station) Number of local bus devices that can be connected: max. 63 (observe current consumption) PROFINET Device function: PROFINET controller, PROFINET device Specification: Version 2.3 Update rate: min. 32 ms (16 devices) min. 32 ms (8 devices) min. 16 ms (4 devices) min. 8 ms (2 devices) min. 4 ms (1Ãdevice) Conformance Class: A Number of supported devices: max. 16 (at PROFINET controller) Supported functions: MRP Device ID: 0093hex Vendor ID: 00B0hex Function Diagnostics display: No Controller redundancy: yes Safety function: No Functionality Programming languages supported: Instruction list (IL) Symbolic flowchart (SFC) Ladder diagram (LD) Function block diagram (FBD) Structured text (ST) System requirements Engineering tool: PC Worx PC Worx Express Configuration tool: Config+ Version 1.01 or later Diagnostics tool: DIAG+ Runtime system: eCLR Application interface: OPC |
Electrical properties | Real-time clock Realtime clock: Yes Description realtime clock: 1.73 s/day = 20Ãppm at 25ðC Potentials Protective circuit: Surge protection of the supply voltage; electronic Polarity reversal protection of the supply voltage; electronic Potentials: Communications power U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 650 mA (with 2ÃA at UBus for the I/Os and UL = 24 V) typ. 100 mA (without I/Os and UL = 24 V) Power consumption: max. 13.2 W (2.0ÃA on UBus, ULÃ=Ã24ÃV) Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Power supply unit: 2 A |
Connection data | AxiolineÃF connector Connection method: Push-in connection Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Interfaces | Web server: yes AxiolineÃF local bus Number of interfaces: 1 Connection method: Bus base module Transmission speed: 100 Mbps Ethernet Bus system: RJ45 Number of interfaces: 2 Connection method: RJ45 jack Note on the connection method: Auto negotiation and autocrossing Transmission speed: 10/100 Mbps (half or full duplex (automatic detection)) Transmission physics: Ethernet in RJ45 twisted pair No. of channels: 2 Service Bus system: USB Number of interfaces: 1 Connection method: Micro USB type B Transmission speed: max. 115.2 kbps No. of channels: 1 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/aad81a7f06bc4f4aa1cf74b52bb32fb4/-S204x204-FJPG Width: 45 mm Height: 126.1 mm Depth: 74 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 60°C up to 2000Ãm above mean sea level -25°C ... 55°C up to 3000Ãm above mean sea level Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (according to DINÃENÃ61131-2, non-condensing, no ice formation) Permissible humidity (storage/transport): 5 % ... 95 % (according to DINÃENÃ61131-2, non-condensing, no ice formation) Shock (operation): 10g (Bump endurance test according to DIN EN 60068-2-27) Vibration (operation): 5g Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 58 kPa ... 106 kPa (up to 4500Ãm above mean sea level) |
Approvals | UL, USA/Canada Identification: cULus Certificate: E238705 |
EMC data | Conformance with EMC directives: Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)ENÃ61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Electromagnetic fieldsENÃ61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Fast transients (burst)ENÃ61000-4-4/IEC 61000-4-4 Criterion B, 2ÃkV Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)ENÃ61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ñ0.5 kV/ñ0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ñ1 kV Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Conducted interferenceENÃ61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V Noise emission test in accordance with ENÃ61000-6-3/IEC 61000-6-3 ClassÃB Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU |
Mounting | Mounting type: DIN rail mounting Connection method: Push-in connection |
Description other products