AXL F DOR4/2 AC/220DC 1F - Relay Module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/c1416576ed7aaf4e91ee7183ca7f3cde/-S204x204-FJPG Width: 53.6 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Input address area: 0 Byte Output address area: 1 Byte Required parameter data: 1 Byte Required configuration data: 6 Byte |
Output data | Relay Number of outputs: 4 (floating) Connection method: Push-in connection Connection technology: 2-conductor Contact switching type: N/O contact Switching current: max. 8 A AC (cos phi = 1) For DC see load limit curve, e.g.,Ãthe following values: max. 8 AÃDC (ââ°¤ 30 V, ohmic load) max. 500 mA DC (110 V, ohmic load) max. 250 mA DC (220 V DC, ohmic load) max. 220 mA DC (125 V DC, L/R ââ°¤ 50 ms, applications with UL approval) max. 110 mA DC (250 V DC, L/R ââ°¤ 50Ãms, applications with UL approval) Switching capacity: max. 2000 VA For DC see load limit curve, e.g.,Ãthe following values: max. 240 W (30ÃVÃDC) max. 55 W (ââ°¥Ã60ÃVÃDC) max. 25 W (125 V DC, 250 V DC, applications with UL approval) Switching capacity in accordance with IEC 60947-5-1: 6 A (120ÃV (AC15)) 3 A (240ÃV (AC15)) 0.22 A (125ÃV (DC13)) 0.1 A (250ÃV (DC-13)) Switching frequency: max. 6 (per minute) Mechanical service life: 10x 106 cycles |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (observe temperature and current derating) Scope of delivery: including bus base module and AxiolineÃF connectors Insulation characteristics Overvoltage category: III (EN 61010-2-201/UL 61010-2-201), up to 2000Ãm above sea level II (EN 61010-2-201/UL 61010-2-201), up to 3000Ãm above sea level Pollution degree: 2 |
Electrical properties | Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 280 mA (all relays pick up) Power consumption: max. 1.4 W (all relays pick up) Electrical isolation/isolation of the voltage ranges Test voltage: Relay contact / logic: 4 kV 5 kV Test voltage: Relay contact / functional ground: 4 kV 5 kV Test voltage: Relay contact/relay contact (open contact): 1 kV, 50 Hz, 1 min. Test voltage: Relay contact/relay contact (adjacent male connectors): 2.5 kV |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã Axioline F: system and installationâ⬠user manual. When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30ÃK above the ambient temperature. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã Axioline F: system and installationâ⬠user manual. When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30ÃK above the ambient temperature. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (max. 6ÃA/channel for wall mounting on horizontal DIN rail; max. 4ÃA/channel for any mounting position) -25°C ... 50°C (max. 8ÃA/channel for wall mounting on horizontal DIN rail; max. 6ÃA/channel for any mounting position) -25°C ... 40°C (max. 8ÃA/channel for any mounting position) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (observe temperature and current derating) |