Industrial Automation

| Product properties | Product type: Interference filters Insulation characteristics Protection class: II Degree of pollution: 2 |
| Electrical properties | Number of phases: 1.00 |
| Input data | AC operation Input voltage range: 100 VÃAC ... 240 VÃAC ñ10Ã% Frequency range (fN): 50 Hz ... 60 Hz ñ10Ã% Current consumption: ââ°¤ 7 A (depending on the power supply) Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C or comparable) Voltage drop, input/output: ââ°¤ 0.35 VÃAC |
| Output data | Output voltage: UIn - |
| Dimensions | Item dimensions Width: 35 mm Height: 105 mm Depth: 114 mm 107 mm (Device depth (DIN rail mounting)) Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 20 mm / 50 mm |
| Material specifications | Flammability rating according to UL 94: V0 |
| Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (DeratingÃ>60°C: 2.5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: ââ°¤ 2000 m Max. permissible relative humidity (operation): ââ°¤ 95 % (non-condensing) |
| Standards and regulations | Overvoltage category EN 61010-1: IIIÃ(ââ°¤Ã2000Ãm) |
| Mounting | Mounting type: DIN rail mounting Mounting position: horizontal DIN rail NS 35, EN 60715 |
Description other products