PHOENIX CONTACTNot available

PV-FT-CF-C-6-750-BK - Device connector front mounting

Device connector front mounting, Range of articles: SUNCLIX, housing material: PPE, number of positions: 1, Connection method: Crimp, cable length: 750
Product Code: 1622792
Partner cod.: 1622792
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
NotesSafety note
Safety note: • WARNING: Commission properly functioning products only. The products must be regularly inspected for damage. Decommission defective products immediately. Replace damaged products. Repairs are not possible.
• WARNING: Only electrically qualified personnel may install and operate the product. They must observe the following safety notes. The qualified personnel must be familiar with the basics of electrical engineering. They must be able to recognize and prevent danger. The relevant symbol on the packaging indicates that only personnel familiar with electrical engineering are allowed to install and operate the product.
WARNING: The connectors may not be plugged in or disconnected under load. Ignoring the warning or improper use may damage persons and/or property.
• The products are suitable for applications in plant, controller, and electrical device engineering.
• Assembled products may not be manipulated or improperly opened.
• Only use mating connectors that are specified in the technical data of the standards listed (e.g. the ones listed in the product accessories online at phoenixcontact.com/products).
• When using the product in direct connection with third-party manufacturers, the user is responsible.
• For operating voltages > 50 V AC, conductive connector housings must be grounded
• Ensure that the protective or functional ground has been properly connected.
• Observe the corresponding technical data. You will find information:
o On the product
o On the packing label
o In the supplied documentation
o Online at phoenixcontact.com/products under the product
• The installation notes/Design In documents online on the download page at phoenixcontact.com/products must be observed for this product.
• Use a protective cap to protect connectors that are not in use. The suitable accessories are available online in the accessory section of the product at phoenixcontact.com/products
• The connector warms up in normal operation. Depending on the ambient conditions, the surface of the connector can continue to warm up. In this case, the user is responsible for posting warnings (e.g. DIN EN ISO 13732-1:2008-12).
• Operate the connector only when it is fully plugged in and interlocked.
• Ensure that when laying the cable, the tensile load on the connectors does not exceed the upper limit specified in the standards.
• Observe the minimum bending radius of the cable. Lay the cable without twisting it.
Product propertiesProduct type: Panel feed-through
Product family: SUNCLIX
Number of positions: 1
Data management status
Article revision: 08
Insulation characteristics
Degree of pollution: 2
DimensionsWidth: 18.6 mm
Height: 18.6 mm
Length: 43.2 mm
Electrical propertiesRated voltage (III/2): 1000 V
Rated surge voltage (III/2): 12 kV
Rated current (6.0 mm²): 40 A
Contact resistance: ≤ 0.45 mΩ (when plugged in (without cable))
Mechanical propertiesMechanical data
Insertion/withdrawal cycles: 100
Insertion force: 45 N ±10 N
Withdrawal force: 250 N ±50 N (when locked)
Material specificationsColor of the housing part: black
Flammability rating according to UL 94: V0
Insulating material group: III
Seal material: EPDM
Housing material: PPE
Cable seal material: Elastosil LR 3065/50
Contact carrier material: PPE
O-ring material: Silopren LSR 2660
Outer sheath, material: PE-X
Cable/lineCable length: 750 mm
Cable type: Railway cable
Railway cable Radox GKW-S
Structure of individual litz in acc. with VDE 0295 / smallest wire diameter: 84x0.3
Cable structure: tin-plated, fine-wired, IEC 60228 Class 5
External cable diameter: 5.10 mm 4.95 mm 5.25 mm ±0.15 mm
Outer sheath, material: PE-X
External sheath, color: black
Single wire, material: Cu
Cable cross section: 6 mm²
Smallest bending radius, fixed installation: 10.2 mm (2x Ø)
Smallest bending radius, movable installation: 15.3 mm (3x Ø)
Halogen-free: yes
Resistance to oil: yes
Flame resistance: yes
Environmental and real-life conditionsAmbient conditions
Degree of protection (when plugged in): IP66 / IP68 (2 m / 24 h)
Degree of protection (not plugged in): IP20
Degree of protection: IP66 / IP68 (2 m / 24 h)
Ambient temperature (operation): -40 °C ... 85 °C
Ambient temperature (assembly): -25 °C ... 50 °C
Resistance to oil: yes
Standards and regulationsFlame resistance: yes
Resistance to oil: yes