Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1350427
PHOENIX CONTACTNot available

PTVME 6/S RD - Test disconnect terminal block

Test disconnect terminal block, nom. voltage: 1000 V, nominal current: 30 A, connection method: Push-in connection, Rated cross section: 6 mm2, cross section: 0.5 mm2 - 6 mm2 , color: red
Product Code: 1350427
Partner cod.: 1350427
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Description
Tecnichal data
Product propertiesProduct type: Test disconnect terminal block
Number of connections: 2
Number of rows: 1
Potentials: 1
Data management status
Article revision: 01
Insulation characteristics
Overvoltage category: III
Degree of pollution: 3
Electrical propertiesRated surge voltage: 8 kV
Maximum power dissipation for nominal condition: 1.31 W
Connection dataNumber of connections per level: 2
Nominal cross section: 6 mm²
Level 1+2
Stripping length: 10 mm ... 12 mm
Internal cylindrical gage: A4
B4
Connection in acc. with standard: IEC 60947-7-1
Conductor cross section rigid: 0.5 mm² ... 6 mm²
Cross section AWG: 20 ... 10 (converted acc. to IEC)
Conductor cross section flexible: 0.5 mm² ... 6 mm²
Conductor cross section, flexible [AWG]: 20 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 6 mm² Connection only with corresponding crimp versions.
Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 6 mm² Connection only with corresponding crimp versions.
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve): 0.5 mm² ... 2.5 mm²
Nominal current: 30 A (with 6 mm² conductor cross section)
Maximum load current: 30 A (with 6 mm² conductor cross section)
Nominal voltage: 1000 V
Nominal cross section: 6 mm²
Level 1+2 Connection cross sections directly pluggable
Conductor cross section rigid: 0.75 mm² ... 6 mm²
Conductor cross-section flexible (ferrule without plastic sleeve): 1.5 mm² ... 6 mm² Connection only with corresponding crimp versions.
Flexible conductor cross section (ferrule with plastic sleeve): 1 mm² ... 6 mm² Connection only with corresponding crimp versions.
DimensionsWidth: 8.2 mm
End cover width: 2.2 mm
Height: 82 mm
Depth on NS 35/7,5: 54.5 mm
Depth on NS 35/15: 62 mm
Material specificationsColor: red (RAL 3001)
Flammability rating according to UL 94: V0
Insulating material group: I
Insulating material: PA
Static insulating material application in cold: -60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 125 °C
Relative insulation material temperature index (Elec., UL 746 B): 125 °C
Electrical testsSurge voltage test
Test voltage setpoint: 9.8 kV
Result: Test passed
Temperature-rise test
Requirement temperature-rise test: Increase in temperature ≤ 45 K
Result: Test passed
Short-time withstand current 4 mm²: 0.5 kA
0.15 kA
1.25 kA
Power-frequency withstand voltage
Test voltage setpoint: 2.2 kV
Result: Test passed
Mechanical propertiesMechanical data
Open side panel: Yes
Mechanical testsMechanical strength
Result: Test passed
Test for conductor damage and slackening
Rotation speed: 10 rpm
Revolutions: 135
Conductor cross section/weight: 0.5 mm² / 0.3 kg
6 mm² / 1.4 kg
Result: Test passed
Environmental and real-life conditionsAging
Result: Test passed
Needle-flame test
Time of exposure: 30 s
Result: Test passed
Oscillation/broadband noise
Specification: DIN EN 50155 (VDE 0115-200):2018-05
Spectrum: Service life test category 2, bogie-mounted
Frequency: f1 = 5 Hz to f2 = 250 Hz
ASD level: 6.12 (m/s²)²/Hz
Acceleration: 3.12g
Test duration per axis: 5 h
Test directions: X-, Y- and Z-axis
Result: Test passed
Shocks
Pulse shape: Half-sine
Acceleration: 30g
Shock duration: 18 ms
Number of shocks per direction: 3
Test directions: X-, Y- and Z-axis (pos. and neg.)
Result: Test passed
Ambient conditions
Ambient temperature (operation): -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport): -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly): -5 °C ... 70 °C
Ambient temperature (actuation): -5 °C ... 70 °C
Permissible humidity (operation): 20 % ... 90 %
Permissible humidity (storage/transport): 30 % ... 70 %
Standards and regulationsConnection in acc. with standard: IEC 60947-7-1
MountingMounting type: NS 35/15
NS 35/7,5
Description
PTVME 6/S RD Morsetto sez.x conv.misura