Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/20 A
Product Code: 1343940
Partner cod.: 1343940
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Input dataControl input (configurable) Rem: Output power ON/OFF (SLEEP MODE)
Default: Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Network type: Star network
Nominal input voltage range: 3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range: 3x 400 V AC ... 500 V AC -20 % ... +10 %
2x 400 V AC ... 500 V AC -10 % ... +10 %
Typical national grid voltage: 400 V AC
480 V AC
Voltage type of supply voltage: AC
Inrush current: typ. 2 A (at 25 °C)
Inrush current integral (I2t): < 0.1 A2s
Inrush current limitation: 2 A (after 1 ms)
AC frequency range: 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN): 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time: typ. 33 ms (3x 400 V AC)
typ. 33 ms (3x 480 V AC)
Current consumption: 3x 0.99 A (400 V AC)
3x 0.81 A (480 V AC)
2x 1.62 A (400 V AC)
2x 1.37 A (480 V AC)
3x 0.8 A (500 V AC)
2x 1.23 A (500 V AC)
Nominal power consumption: 541 VA
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi): 0.94
Switch-on time: < 1 s
Typical response time: 300 ms (from SLEEP MODE)
Recommended breaker for input protection: 3x 4 A ... 20 A (Characteristic B, C or comparable)
Recommended fuse for input protection: ≥ 300 V AC
Discharge current to PE: < 3.5 mA
1.7 mA (550 V AC, 60 Hz)
DC operation
Nominal input voltage range: ± 260 V DC ... 300 V DC
Input voltage range: ± 260 V DC ... 300 V DC -13 % ... +30 %
Voltage type of supply voltage: DC
Current consumption: 1.23 A (± 260 V DC)
1.06 A (±300 V DC)
Recommended breaker for input protection: 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection: ≥ 1000 V DC
Output dataEfficiency: typ. 93.9 % (400 V AC)
typ. 93.8 % (480 V AC)
Output characteristic: U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN): 20 A
Static Boost (IStat.Boost): 25 A
Dynamic Boost (IDyn.Boost): 30 A (5 s)
Selective Fuse Breaking (ISFB): 120 A (15 ms)
Magnetic circuit breaker tripping: A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating: > 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): ≤ 32 V DC
Control deviation: < 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple: < 60 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 480 W
600 W
720 W
Apparent power: 686 VA (400 V, UOUT = 24 V, IOUT = stat. Boost)
698 VA (480 V, UOUT = 24 V, IOUT = stat. Boost)
Maximum no-load power dissipation: < 7 W (400 V AC)
< 7 W (480 V AC)
Power loss nominal load max.: < 32 W (400 V AC)
< 33 W (480 V AC)
Power dissipation SLEEP MODE: < 5 W (400 V AC)
< 5 W (480 V AC)
Crest factor: typ. 1.78 (400 V AC)
typ. 2.1 (480 V AC)
Rise time: < 80 ms (UOut = 10 % ... 90 %)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal
Signal ground SGnd: Reference potential for Out1, Out2, and Rem
Signal Out 1 (configurable)
Digital: 24 V DC 20 mA
Default: 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet
Signal Out 2 (configurable)
Digital: 24 V DC 20 mA
Analog: 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default: 24 V DC 20 mA 24 V DC for POut < PN
Signal relay 13/14 (configurable)
Default: closed (Uout > 0.9 USet)
Digital: 24 V DC 1 A
30 V AC/DC 0.5 A
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
SignalingTypes of signaling: LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal output
POut: > 100 % (LED lights up yellow, output power > 480 W)
> 75 % (LED lights up green, output power > 360 W)
> 50 % (LED lights up green, output power > 240 W)
UOut: > 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)
Electrical propertiesNumber of phases: 3.00
Insulation voltage input/output: 4 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE: 0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency: 90.00 kHz ... 110.00 kHz (Auxiliary converter stage)
56.00 kHz ... 500.00 kHz (Main converter stage)
25.00 kHz ... 500.00 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 985000 h (25 °C)
> 638000 h (40 °C)
> 311000 h (60 °C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 10 A
Temperature: 40 °C
Time: 344000 h
Additional text: 400 V AC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 10 A
Temperature: 40 °C
Time: 320000 h
Additional text: 480 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 25 °C
Time: 445000 h
Additional text: 400 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 25 °C
Time: 432000 h
Additional text: 480 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 40 °C
Time: 157000 h
Additional text: 400 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 40 °C
Time: 152000 h
Additional text: 480 V AC
DimensionsDimensional drawing: https://caas.phoenixcontact.com/caas/v1/stable/media/170842/full/b1500?format=jpg
Width: 70 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 73 mm
MountingMounting type: DIN rail mounting
Assembly note: alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: yes
Material specificationsFlammability rating according to UL 94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Ambient temperature (start-up type tested): -40 °C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
Standards and regulationsRail applications: EN 50121-3-2
EN 50121-4
EN 50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant
Standard âۉ€œ Limitation of mains harmonic currents: EN 61000-3-2
Standard - Electrical safety: IEC 61010-2-201 (SELV)
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard - Safety of transformers: EN 61558-2-16
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMI F47-0706, EN 61000-4-11
Overvoltage category
EN 61010-1: II (≤ 2000 m)
EN 62477-1: III (≤ 2000 m)
ApprovalsCSA: CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
Shipbuilding approval: DNV GL, PRS, BV, LR, ABS
SIQ: BG (type approved)
UL approvals: UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataEMC requirements for noise emission: EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity: EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant: IEC 61850-3