Industrial Automation
AXL SE DO4/2 2A EF - Digital module


Dimensions | Dimensional drawing: https://caas.production.phoenixcontact.coremedia.cloud/caas/v1/stable/media/22530/full/b250?format=jpg Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Interfaces | SmartÃElement interface Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the SmartÃElement. Start time until ready to operate: < 500 ms |
System properties | Module ID code (hex): none Process data channel: 8 bit Input address area: 1 Byte Output address area: 1 Byte Required parameter data: 3 Byte Required configuration data: 7 Byte |
Output data | Digital Output name: Digital outputs Connection method: Push-in connection Connection technology: 2-conductor Number of outputs: 4 Protective circuit: Short-circuit and overload protection; electronic Output voltage: 24 VÃDC Maximum output current per module: max. 8 A (provide external fuse protection; observe the derating.) Nominal output voltage: 24 VÃDC Load min.: 10 ké Output voltage when switched off: max. 1 V Output current when switched off: max. 300 õA Nominal load, inductive: 48 VA (1.2 H, 12 é, at 24ÃVÃDC) Nominal load, lamp: 24 W (at 24 V DC) Nominal load, ohmic: 48 W (12 é, in the supply voltage range) Switching frequency: max. 1200 per second (With resistive load, at least 50ÃmA load current) max. 1 per second (with inductive load) max. 4 per second (with nominal lamp load) Behavior with overload: Shutdown with automatic restart Behavior with inductive overload: Output can be destroyed Signal delay: max. 100 õs (when switched on) max. 100 õs (when switched off, with at least 50 mA load current) Overcurrent shut-down: min. 2.8 A Output current with ground connection interrupt when switched off: < 1 mA |
Product properties | Type: modular Product type: I/O component Product family: Axioline SmartÃElements Mounting position: See the system in which the SmartÃElement is used. Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Potentials: I/O supply (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 8 A (provide external protection) Power consumption: max. 240 W (of which 2ÃW constitute internal losses) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; parallel diode Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Electrical isolation/isolation of the voltage ranges Test voltage: Communications power supply / 24 V supply UO (I/O): 500 VÃAC, 50 Hz, 1 min. Test voltage: Communications power supply / 24 V supply UP: 500 VÃAC, 50 Hz, 1 min. Test voltage: Communications supply / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply UO (I/O) / 24 V supply UP: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply UO (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply UP / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: I/O Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃSmartÃElementsâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃSmartÃElementsâ⬠user manual. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: Smart Element slot Mounting position: See the system in which the SmartÃElement is used. |