Industrial Automation
PLC-RPT-230UC/21-21/SO46 - Relay Module


Notes | General: The PLC-ATP partition plate must be installed for voltages greater than 250ÃV (L1, L2, L3) between identical terminal blocks on adjacent modules. The PLC-ATP separating plate should be installed for safe isolation between adjacent modules The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. |
Product properties | Product type: Relay Module Product family: PLC-INTERFACE Application: Filter to prevent interference Operating mode: 100% operating factor Mechanical service life: approx. 3x 107 cycles Insulation characteristics Insulation: Basic insulation Insulation characteristics: Air clearances and creepage distances between the power circuits Insulation: Basic insulation Overvoltage category: III Pollution degree: 3 |
Electrical properties | Maximum power dissipation for nominal condition: 2.3 W Test voltage (Winding/contact): 4 kVrms (50ÃHz, 1Ãmin., winding/contact) Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VÃAC Rated surge voltage: 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths) |
Input data | Coil side Nominal input voltage UN: 230 VÃAC 220 VÃDC Input voltage range: 179.4 VÃAC ... 264.5 VÃAC (20ðC) 171.6 VÃDC ... 253 VÃDC (20ðC) Mains frequency: 50/60 Hz Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 8.5 mA (50ÃHz) 10 mA (60ÃHz) Typical response time: 7 ms Typical release time: 10 ms Typical release voltage: 60 VÃAC Coil voltage: 110 VÃDC Protective circuit: RC element Bridge rectifier Status display: Yellow LED |
Output data | Switching Contact switching type: 2 changeover contacts Type of switch contact: Single contact Contact material: AgNi Maximum switching voltage: 250 V AC/DC Minimum switching voltage: 5 V (10ÃmA) Limiting continuous current: 6 A Maximum inrush current: 15 A (300Ãms) Min. switching current: 10 mA (5 V) Interrupting rating (ohmic load) max.: 144 W (24ÃVÃDC) 96 W (48ÃVÃDC) 60 W (60ÃVÃDC) 44 W (110ÃVÃDC) 57 W (220ÃVÃDC) 1500 VA (250ÃVÃAC) Switching capacity min.: 0.12 W Switching capacity: 2 A (DC13, 24ÃV) 0.2 A (DC13, 250ÃV) 3 A (AC15, 24ÃV) 3 A (AC15, 250ÃV) |
Connection data | Connection method: Push-in connection Stripping length: 10 mm Conductor cross section rigid: 0.14 mm² ... 2.5 mm² Conductor cross section flexible: 0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1 mm² (TWIN ferrule) Conductor cross section AWG: 26 ... 14 |
Dimensions | Width: 14 mm Height: 80 mm Depth: 94 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection (Relay base): IP20 (Relay base) Degree of protection (Relay): RT III (Relay) Degree of protection (Installation location): IP54 (Installation location) Ambient temperature (operation): -40°C ... 55°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ââ°¤ 2000 m |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant Shipbuilding approval Certificate: TAE0000196 Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group ENÃ60068-2-60 DNV GL data Temperature: D Humidity: A Vibration: B/C EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive Electromagnetic compatibility: Conformance with EMC directive |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: IEC 60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
Description other products