PHOENIX CONTACT 1115674
PHOENIX CONTACT 1115674
PHOENIX CONTACTNot available

CAPAROC CR EXT20 - Busbar

Extension busbar with 20 slots for the CAPAROC system. For installation on a DIN rail.
Product Code: 1115674
Partner cod.: 1115674
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
NotesGeneral
Note: LABS release âۉ€œ in accordance with test specification VWÂPVÂ3.10.7:2005-0
When using CAPAROC E1... modules, for continuous shock in accordance with IEC 60068-2-27 the 6ÂmsÂ/Â15g degree of severity applies
Product propertiesProduct type: Device circuit breakers
Product family: CAPAROC
Number of slots: 20
Insulation characteristics
Protection class: III
Pollution degree: 2
Electrical propertiesGeneral
Rated voltage: 24 VÂDC
Rated current IN: 45 AÂDC (Total current input)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f9c16e9b519ee9488cec24911bd55912/-S204x204-FJPG
Width: 133.6 mm
Height: 44 mm
Depth: 22.5 mm (incl. DIN rail 7.5Âmm)
Material specificationsMaterial: Copper
PC
Flammability rating according to UL 94: V-0
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -30°C ... 65°C (The temperature range of the power module must be taken into consideration)
Ambient temperature (storage/transport): -40°C ... 70°C
Altitude: ≤ 4000 m (amsl)
Humidity test: 96Âh, 95Â%ÂRH, 40°C
Shock (operation): 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27)
25g (6Âms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock)
15g (6Âms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock. If more than six CAPAROC E1 modules are used in the system.)
Vibration (operation): 5g (10 ... 150ÂHz / 10Âcycles / axis / X,ÂY,ÂZ)
ApprovalsUL approval
Identification: UL/C-UL Listed UL 508
UL 121201 Class I, Division 2, Groups A, B, C, D, T4A
Standards and regulationsStandards/specifications: ENÂ61000-6-2
ENÂ61000-6-3
ENÂ60068-2-78
ENÂ50178
ENÂ60068-2-6
ENÂ60068-2-27
Note: EMC âۉ€œ Immunity for industrial areas
EMC âۉ€œ Emission for residential, business and commercial properties and small operations
Environmental influences âۉ€œ Moisture and heat, constant
Equipping power installations with electronic equipment
Environmental influences âۉ€œ Vibrations (sinusoidal)
Environmental influences âۉ€œ Shocks
MountingMounting type: DIN rail: 35 mm
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00466.pdf

Approvals_00467.pdf

Flyer_00004.pdf

Flyer_00005.pdf

Manufacturer_declaration_01431.pdf

Manufacturer_declaration_02457.pdf

Manufacturer_declaration_05487.pdf

Package_slip_00239.pdf

Technical_drawing_08890.pdf

Various_00001.pdf