Industrial Automation
AXL F BK PN TPS XC - Bus coupler


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/63211ccd321d8a40a4dac68a1b46b1ae/-S204x204-FJPG Width: 45 mm Height: 126.93 mm Depth: 75 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Interfaces | PROFINET Number of interfaces: 2 Connection method: RJ45 jack Note on the connection method: Auto negotiation and autocrossing Transmission speed: 100 Mbps (full duplex) Transmission physics: Ethernet in RJ45 twisted pair AxiolineÃFÃlocal bus Number of interfaces: 1 Connection method: Bus base module Transmission speed: 100 Mbps Service Number of interfaces: 1 Connection method: USB type C |
System properties | System limits Number of supported devices: max. 63 (per station) Number of local bus devices that can be connected: max. 63 PROFINET Device function: PROFINET device Specification: Version 2.3 Conformance Class: Conformance-Class C Device ID: 1000hex Vendor ID: 00B0hex |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any Scope of delivery: including bus base module and AxiolineÃF connector Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Potentials: Communications power U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 690 mA (2.0ÃA on UBus, ULÃ=Ã24ÃV) Power consumption: max. 13.5 W (2.0ÃA on UBus, ULÃ=Ã24ÃV) Protective circuit: Surge protection; electronic Reverse polarity protection; electronic Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Power supply unit: max. 2 A Electrical isolation/isolation of the voltage ranges Test voltage: PROFINET interface 1 / PROFINET interface 2: 1500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 1 / 24 V communications voltage (UL) feed-in: 1500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 2 / 24 V communications voltage (UL) feed-in: 1500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 1 / functional ground: 1500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 2 / functional ground: 1500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V communications voltage (UL) feed-in / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zoneÃ2 potentially explosive area) -40°C ... 70°C (Extended, see section ââ¬Ã Tested successfully: use under extreme ambient conditionsâ⬠in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Approvals | ATEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: UL 20 ATEX 2441X UKEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: PxCIMA22UKEX2701949X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx ULD 20.0026X UL, USA/Canada Identification: cULus Certificate: E238705 UL Ex, USA / Canada Identification: Class I, Zone 2, AEx ec IIC T4 ClassÃI, DivisionÃ2, Groups A, B, C, D, T4 Ex ec IIC T4 Gc X Certificate: E366272 CCCÃ/ÃChina-Ex Identification: Ex ec IIC T4 Gc Certificate: ïì, 2021122309114456 |
Mounting | Mounting type: DIN rail mounting Mounting position: any |
Description other products