Industrial Automation
AXL F IOL8 2H - Communication module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/97375d412c926547bb2e1a41b7a47993/-S204x204-FJPG Width: 35 mm Height: 129.9 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Process data channel: 512 bit Input address area: 64 Byte Output address area: 64 Byte |
Input data | Digital Description of the input: IO-Link ports in digital input (DI) mode Number of inputs: max. 8 (EN 61131-2 type 1) Connection method: Push-in connection Connection technology: 3-conductor Nominal input voltage UIN: 24 VÃDC Input voltage range "0" signal: -0.3 VÃDC ... 5 VÃDC Input voltage range "1" signal: 11 VÃDC ... 30 VÃDC Nominal input current: typ. 2.5 mA Sensor current per channel: max. 1 A (from L+/L-) Input filter time: 1 õs IO-Link Number of ports: 8 Connection method: Push-in connection Connection technology: 3-conductor Port type: Class A |
Output data | Digital Output description: IO-Link ports in digital output (DO) mode Connection method: Push-in connection Connection technology: 2-, 3-conductor Number of outputs: max. 8 Nominal output voltage: 24 VÃDC Nominal current per channel: 200 mA |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineÃF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Supply: IO-Link Nominal voltage for I/O supply: 24 VÃDC Supply voltage range: 18 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Nominal current for every IO-Link port: 1 A (at L+/L-) 200 mA (at C/Q) Protective circuit: Overload protection for L+; electronically limited to 1.2ÃA Short-circuit protection for L+; by switching off after 5Ãms Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 50 mA Power consumption: max. 250 mW Potentials: Feed-in of the supply voltage for the I/O devices (U Supply voltage: 24 VÃDC Supply voltage range: 18 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 8 A (in total, current consumption of I/O circuit and at C/Q as DO and at L+/L-) max. 60 mA (without connected peripherals) Power consumption: max. 192 W Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; parallel diode; with external 5ÃA fuse (only for commissioning) Electrical isolation/isolation of the voltage ranges Test voltage: 5ÃV supply of the local bus (UBus) / 24ÃV supply (I/Os): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |