Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1105681
PHOENIX CONTACT 1105681
PHOENIX CONTACTNon disponibile

FA MCR-EX-HT-TS-I-OLP - Head-mounted transducer

Ex i-Output loop-powered head transmitter for transmitting up to 2 sensor signals from RTD and TC sensors as well as from resistance and voltage sensors via 4 mA ... 20 mA. HART, Standard configuration, Safety Integrity Level (SIL, IEC 61508): 2, Systematic Capability: 3, Screw connection
Cod. Articolo: 1105681
Cod. Fornitore: 1105681
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Caratteristiche Tecniche
Product propertiesProduct type: Temperature transmitter
Product family: Field Analog
No. of channels: 2
Configuration: Software
HART
Data management status
Article revision: 01
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesStep response (0âۉ€œ99%): 0.8 s (TC)
Electrical isolation Input/output
Test voltage: 2 kV AC (50 Hz, 60 s)
Supply
Supply voltage range: loop-powered, no external supply necessary
11 V DC ... 42 V DC (Standard)
11 V DC ... 32 V DC (SIL active)
11 V DC ... 30 V DC (Ex)
Input dataMeasurement
Number of inputs: 2
Input voltage range: -20 mV ... 100 mV (Minimum measuring span: 5 mV)
Sensor types (RTD) that can be used: Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC): A, B, C, D, E, J, K, L, N, R, S, T, U
Temperature measuring range: -250 °C ... 2500 °C (Range depending on the sensor type)
-200 °C ... 850 °C (Pt 100)
> 10 K (RTD)
> 50 K (TC)
Linear resistance measuring range: 10 Ω ... 2000 Ω (Minimum measuring span: 10 Ω)
Output dataSignal: Current
Current output signal: 4 mA ... 20 mA (HART)
20 mA ... 4 mA (HART)
Max. current output signal: 23 mA
Load: (UB âۉ€œ 11 V) / 0.023 A
HART coding: FSK ± 0.5 mA
HART version: 7
Transmission speed: 1200 Baud
Mains frequency filter: 50/60 Hz
Communication resistance: ≥ 250 Ω
Switch-on delay: ï‚» 10 s (HART)
ï‚» 28 s (Measured value)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.35 Nm
Ex dataEx installation (EPL): Ga
Div. 1
Ex i circuits (EPL): Gb
Div. 1
InterfacesData communication (bypass)
Protocols supported: HART
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP00 (upon installation in field housing IP66/67, NEMA 4X)
Ambient temperature (operation): -40 °C ... 85 °C
-40 °C ... 70 °C (SIL active)
Ambient temperature (storage/transport): -50 °C ... 100 °C
Altitude: ≤ 4000 m (Above sea level)
Climatic class: C1
Permissible humidity (operation): 5 % ... 95 % (condensation permitted)
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification: ïÃ‹œ II 1G Ex ia IIC T6...T4 Ga
ïÃ‹œ II 2G Ex ia IIC T6...T4 Gb
Certificate: EPS 17 ATEX 1 130 X
IECEx
Identification: Ex ia IIC T6...T4 Ga
Ex ia IIC T6...T4 Gb
Certificate: IECEx EPS 17.0076X
UL, USA/Canada
Identification: UL 61010 Recognized
FM
Identification: NI / Class I / Div. 1, 2 / Group ABCD T6/T5/T4
IS / Class I / Div. 1, 2 / Group ABCD
CSA
Identification: Exia / Class I / Group ABCD T6/T5/T4
Shipbuilding approval
Certificate: DNV GL TAA00002GX
Safety Integrity Level (SIL, IEC 61508)
Identification: 2
Systematic Capability
Identification: 3
DNV GL data
Temperature: D
Humidity: B
Vibration: B
EMC: B
Enclosure: C
MountingMounting type: Installation
DIN rail mounting
Assembly note: Installation in connection head according to DIN 43729 form B
Descrizione
FA MCR-EX-HT-TS-I-OLP Convertitore