Base Module for Bulletin 280 Combination Starter, EtherNet/IP, 25 A Rated Device
Cod. Articolo: 280E-FNS-25-RG
Cod. Fornitore: 280E-FNS-25-RG
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Caratteristiche Tecniche
Degree of protection (IP)IP67
Shipping weight, approx10.4 kg
ShockOperational: 15 G
Wire strip lengthPower and ground terminals: 0.35 inch (9 mm)
VibrationOperational, 1 G, 0.15 mm (0.006 inch) displacement
Tightening torquePower and ground terminals: 4.5 lb.inch per UL/NEMA (secondary terminal)
Mechanical life operationsContactor C23 (AC-3): 13000000 operations per IEC
Disconnect lock outRecommend 8 mm (5/16 inch) lock shackle or hasp. The hasp should not exceed 8 mm (5/16 inch) when closed.
Altitude2000 m
Storage and transportation temperature-25 °C
Humidity5…95% (noncondensing)
Protection against shockPower circuit: IP2X per IEC
Surge transient1 kV (12) L-L, 2 kV (2) L-N (earth)
Radiated emissionsClass A, Group 1, equivalent to C2 emissions
Conducted radio frequency emissions10V rms communications cables, 10V rms (PE), 150 kHz...80 MHz
Radio frequency electromagnetic field10V/m, 80 MHz...1 GHz, 3V/m, 1.4 GHz...2 GHz, 1V/m, 2.0 GHz...2.7 GHz
Degree of protection (NEMA)4
Pollution degree3
Operating temperature, max-20 °C
Electrostatic discharge4 kV contact and 8 kV air
Fast transient2 kV (power), 2 kV (PE), 1 kV (communications and control)
Overload current range3.2 A
Base moduleBase only-safety
Short circuit protection25 A rated device
DHCP timeoutEthernet port: 30 s
Web serverEmbedded web server
Overvoltage categoryControl circuit: III per IEC
Rated operational currentPower circuit: 16 A maximum
Rated impulse voltagePower circuit: 6 kV
IP addressEthernet port: DHCP enabled by default
PortsEthernet port: embedded switch with 2 ports
Rated input operation voltageSourced from control circuit (A3/A2): 24V DC
Input OFF-state currentSourced from control circuit (A3/A3): <1.5 mA
Module inrush currentEtherNet/IP version: 1.09 A (A1/A2 with HOA)
Module steady currentEtherNet/IP version: 0.3 A (A3/A2 without HOA)
Total control power (running)EtherNet/IP version: 7.2 W (A3/A2 without HOA)
Operating frequencyPower circuit: 50/60 Hz
Input ON-state currentSourced from control circuit (A3/A3): 7.2 mA @ 24V DC
Ethernet receptaclesEthernet port: 2 D-coded, 4-pin female M12 connectors
Number of contactsOutput ratings - sourced from control circuit (A1/A2): 2
Voltage status onlySensor source: 11...26.4V DC from unswitched power (A3-A2)
Trip rating120% of full load current (FLC) setting
Type of currentOutput ratings - sourced from control circuit (A1/A2): 24 DC
Input compatibilitySourced from control circuit (A3/A3): IEC 1133 Type 1+ per IEC
ON-state voltage, maxOutput ratings - sourced from control circuit (A1/A2): 1.5V DC
Rated output operation voltageSourced from control circuit (A1/A2): 26.4V DC
Insulation voltagePower circuit: rated 600V
Communication rateEthernet port: 10/100 Mbs with auto negotiate half duplex and full duplex
Dielectric withstandPower circuit: 2500V AC per IEC
Type of contactsOutput ratings - sourced from control circuit (A1/A2): normally open (N.O.)
Current availableSensor source: 50 mA maximum per input, 200 mA for any single point
Type of control circuitOutput ratings - sourced from control circuit (A1/A2): solid state sourcing output
Conventional thermal current (Ith)Output ratings - sourced from control circuit (A1/A2): 0.5 A each, 1 A maximum combined
Circuit breaker operational current rating, max60 A @ 480V (with gland type: RR)
RMS symmetrical amperes30 kA @ 480Y/277V (with gland type: RR)
Rated operation voltagePower circuit: 200...575V
3-phase power/motor cable connectionRound-ArmorStart ST compatible
Input filter - software selectableSourced from control circuit (A3/A2): settable from 0...64 ms in 1 ms increments (ON to OFF)
Fuse operational current rating, max60 A @ 480V (with gland type: RR)
Total control power (pick up)EtherNet/IP version: 7.2 W (A3/A2 without HOA)
Peak output currentOutput ratings - sourced from control circuit (A1/A2): current limited 2-8 Amps (5 amps nominal) @ 24V DC
Trip classClass 10, 15, 20
Operational power ratingFull voltage starters âۉ€œ IP67/NEMA Type 4: 7.5 kW @ 400V AC, 50 Hz (Current rating 3.2...16 A)
DataEthernet port: Transported over both TCP and UDP, Minimum of 500 I/O packets/second (pps), Supports up to 150 concurrent TCP sockets
Input frequency response, maxSourced from control circuit (A3/A2): 200 Hz (DeviceLogix response is greater than 200 Hz, network response depends on control system network performance.)
Device connectionsTCP port supports 5 concurrent incoming connections
Number of digital inputs4
Number of digital outputs2
Application in industrial area permittedYes
Max. output frequency400 Hz
Supporting protocol for EtherNet/IPYes
Mains frequency50/60 Hz
Short circuit protection device performance (SCPD) typeType 1
Utilization categoryPower circuit: AC-3 per IEC
SecurityWeb server: login and password configurable
Input OFF-state voltage rangeSourced from control circuit (A3/A3): 0...5V DC
Input ON-state voltage rangeSourced from control circuit (A3/A3): 10...26V DC
ConfigurationWeb server: Status, diagnostics and configuration tabs
E-mailWeb server: support simple mail transfer protocol (SMTP)
Off-state leakage current, maxOutput ratings - sourced from control circuit (A1/A2): 10 μA
Blocking voltage, maxOutput ratings - sourced from control circuit (A1/A2): 35V DC
Fault recoveryDLR: ring recovery time is less than 3 ms for a 50 node network
DC control voltageEtherNet/IP version: 24V DC (A1/A2, A3/A2, without and without HOA)
Device level ringBeacon-based performance including IEEE 1588 end to end transparent clock
Load typesOutput ratings - sourced from control circuit (A1/A2): resistive or light inductive
Surge suppressionOutput ratings - sourced from control circuit (A1/A2): integrated diode, clamps @ 35V DC
Cycle rate, maxOutput ratings - sourced from control circuit (A1/A2): 30 operations/minute capacitive and inductive loads
Thermo-protectionOutput ratings - sourced from control circuit (A1/A2): integrated short circuit and over current protection
Wire sizePower and ground terminal: 1.0…4.0 mm² per IEC (primary/secondary terminal)
Number of poles3
Specifiche
Module Data
Communications:EtherNet/IP
Enclosure Type:NEMA Type 4 Watertight Enclosure - IP 67
Base Module:Base Module Only
Short Circuit Protection:25 A Rated Device
Line Connection:Round- ArmorStart ST compatible