| Suitable for safety functions | No |
| Digital inputs configurable | Yes |
| Digital outputs configurable | No |
| Voltage type of supply voltage | DC |
| Type of electric connection | Screw connection |
| Total backplane power | 1.7 W |
| Thermal dissipation | 20.4 BTU/h |
| Current draw | 300 mA @ 5.1V, 16 mA @ 24V |
| Module keying | Electronic, software configurable |
| Outputs | 2 current sourcing |
| Power dissipation, max | 6 W @ 60 °C (140 °F) |
| Inputs | Two flowmeters (F) inputs used for all modes, Two gate inputs used in Totalizer mode for prover/store count, 4 (2 per channel) |
| Isolation voltage | 250V (continuous), reinforced insulation type, I/O-to-backplane, 250V (continuous), basic insulation type, I/O group-to-group |
| Wire category | 2 on signal ports, 1 on power ports |
| Redundancy | No |
| Short-circuit protection, outputs available | No |
| High resolution, max | 100 kHz |
| Frequency | Resolution: 0.0005 Hz |
| Slot width | 1 |
| RTB keying | User-defined mechanical |
| Shock | Operating: 30 G, Non operating: 50 G |
| Vibration | 2 G @ 10...500 Hz |
| Surrounding air temperature, max | 60 °C |
| North American temperature code | T4 |
| Emissions | IEC 61000-6-4 |
| ESD immunity | 6 kV contact discharges, 8 kV air discharges |
| Relative humidity | 5...95% noncondensing |
| Conducted RF immunity | 10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports |
| EFT/B immunity | ±4 kV at 5 kHz on unshielded output and power ports, ±4 kV at 5 kHz on shielded input ports |
| Operating temperature | 0 to 60 °C |
| Surge transient immunity | ±1 kV line-line (DM) and ±2 kV line-earth (CM) on unshielded output and power ports, ±2 kV line-earth (CM) on shielded input ports |
| Radiated RF immunity | 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz |
| Nonoperating temperature | -40 °C |
| On-state voltage drop, max | 0.6 é x current |
| Off-state leakage current, max | <300 µA @ 31.2V DC |
| Reverse polarity protection | Outputs only |
| Output switching time | <50 üs turn on, <300 üs turn off, Outputs triggered by Total, all other âturn-onâ and âturn-offâ times <1 ms |
| Output control | Any number of outputs is assignable to any of two flowmeter channels each output can have 2 âturn-onâ and âturn-offâ preset values |
| Output type | IEC 1 A 24V DC |
| Output voltage source | Customer supplied |
| Overload current | Electronic (<4 A) |
| Surge current | 2 A @ 50 ms, repeatable every 2s |
| Output current per point | 1 @ 10...31.2V DC, 20 mA @ 4.5...5.5V DC |
| Output reverse polarity protection | Yes (if wired incorrectly, module outputs can be permanently disabled.) |
| Output short circuit protection | Electronic (no indication of fault. remove overload and toggle output on/off to restore.) |
| Output voltage range, nom | 5V operation: 4.5...5.5V DC for 3...20 mA load per point, 12/24V operation: 10...31.2V DC for 40 mA...1 A load per point |
| Input frequency, max | 100 kHz @ flowmeter inputs (overrange occurs at 100 kHz) |
| Gate input on-state current, min | 4 mA |
| Gate input on-state current, nom | 15 mA |
| Input sampling period | User selectable |
| Count range, max | 2, 147, 483, 647 |
| Flowmeter input impedance | 5 ké ±30% resistive |
| Mechanical filter debouncing (Z0 & Z1 Inputs) | Software selectable |
| Gate input voltage range | 5V operation: 4.5...5.5V DC, 12/24V operation: 10...26.4V DC |
| Filtering (inputs F0 & F1) | Firmware selectable: high-speed 100 kHz or low-pass filter for frequencies <70 Hz |
| Flowmeter input voltage | ±30V, selectable input thresholds of 50 mV, 1.3V and 4V: ±30V peak unterminated open circuit voltage, magnetic pickup, TTL compatible, input voltage >1.3V DC is Logic 1 and -0.7...1.3V DC is Logic 0, 12...24V DC powered preamp output, 4V DC threshold |
| Totalizer fill and prover | Yes |
| Enclosure type | None (open-style) |