ROCKWELL AUTOMATION 140MG-J8P-D17-UJ-BA
ROCKWELL AUTOMATIONNon disponibile

Mtr Protection Ckt-Bkr, 250A J Frame, 35..65 kA at 480V (MCP), MCP (no thermal protection), Default (3 Poles), 175A, 80 Percent MCCB, Blank, No Bus Bar Mounting, 250V AC/DC, 24…30V AC/DC, Undervoltage release, 2 Aux + Alarm

140MG - Motor Circuit Protectors, J frame, 35..65 kA at 480V, MCP (magnetic only), Rated Current 175 A, Undervoltage Release 24...30V AC/DC, 2 NO/NC AUX + Alarm, 250V
Cod. Articolo: 140MG-J8P-D17-UJ-BA
Cod. Fornitore: 140MG-J8P-D17-UJ-BA
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Caratteristiche Tecniche
Number of poles3
Number of auxiliary contacts as change-over contact2
With integrated under voltage releaseYes
Rated permanent current Iu175 A
Type of control elementToggle
Rated impulse withstand voltage (Uimp)8 kV
Frame size250 A
Magnetic trip currentCam setting I: 1750 A
Hp rating40 Hp @ 230V, 3-phase
Watt loss27.3 W
Insulation voltage (Ui)Rated 1000V per IEC
KW rating, max90 kW @ 400/415V, 3-phase
Rated ultimate short-circuit breaking capacity for Type D combination (Icu)65 kA @ 440V AC per IEC 60947-2/GB 14048.2
Electrical life cycle8000 @ 415V AC
Rated service short-circuit breaking capacity for Type D combination (Ics)100% of Icu @ 690V AC per IEC 60947-2/GB 14048.2
Instantaneous trip setting150 to 250 A
Rated ultimate short-circuit breaking capacity (Icu)70 kA @ 500V DC, 3-poles in series per IEC 60947-2/GB 14048.2
Rated service short-circuit breaking capacity (Ics)100% of Icu @ 690V AC per IEC 60947-2/GB 14048.2
Protection typeAdjustable magnetic only (less than 13 x In)
Motor drive integratedNo
With switched-off indicatorNo
Motor drive optionalYes
Position of connection for main current circuitFront side
Type of electrical connection of main circuitScrew connection
Interrupting rating/breaking capacity35...65 kA at 480V
Instantaneous trip rating(SCCR) circuit breaker per NEMA, UL, CSA, for combination controller 65 kA @ 480V AC
Degree of protection (IP)IP20
Weight5.5 lb
Mechanical life operations25000 /h
Factory optionUnder voltage release, 24...30V AC/DC
Height6.3 mm
Width4.13 mm
Depth82.5 mm
Operating temperature-13 °F
Storage temperature-40 °F
Wire temperature ratingAl or Cu 75°C
Ambient temperature without derating104°F @ 40°C