Input data | AC operation Network type: Star network Nominal input voltage range: 3x 400 VÃAC ... 500 VÃAC 2x 400 VÃAC ... 500 VÃAC Input voltage range: 3x 400 VÃAC ... 500 VÃAC -20Ã%Ã...Ã+15Ã% 2x 400 VÃAC ... 500 VÃAC -10Ã%Ã...Ã+15Ã% Input voltage range AC: 3x 320 VÃAC ... 575 VÃAC Typical national grid voltage: 3x 400 VÃAC 3x 480 VÃAC Voltage type of supply voltage: AC Inrush current: ââ°¤ 26 A (typical) Inrush current integral (I2t): ââ°¤ 0.3 A2s AC frequency range: 50 Hz ... 60 Hz Mains buffering time: typ. 10 ms (400ÃVÃAC) typ. 20 ms (500 VÃAC) Current consumption: 3x 0.6 A (400ÃVÃAC) 3x 0.6 A (500 VÃAC) 2x 1.1 A (400ÃVÃAC) 2x 1.1 A (500 VÃAC) Nominal power consumption: 451.7 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.58 Typical response time: < 1 s Input fuse: 3.15 A (internal (device protection), slow-blow) Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA < (550 V AC, 60 Hz)
|
Output data | Efficiency: > 92 % (at 400 V AC and nominal values) Output characteristic: U/I with dynamic load reserve Nominal output voltage: 24 VÃDC ñ1Ã% Setting range of the output voltage (USet): 24 VÃDC ... 28 VÃDC (> 24 VÃDC, constant capacity restricted) Nominal output current (IN): 10 A Dynamic Boost (IDyn.Boost): 15 A (5 s) Derating: > 60°C ... 70°C (2.5%/K) Protection against overvoltage at the output (OVP): ââ°¤ 30 VÃDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ñ10 %) Residual ripple: ââ°¤ 20 mVPP Short-circuit-proof: yes No-load proof: yes Output power: 240 W 360 W Maximum no-load power dissipation: < 1.1 W (400ÃVÃAC) Power loss nominal load max.: < 22 W (480ÃVÃAC) Rise time: ââ°¤ 120 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK Continuous load current: 100 mA Signal relay 13/14 Default: closed Digital: 30 VÃAC 30 VÃDC 100 mA
|
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm² Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm² Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm² Single conductor/terminal point, stranded, with ferrule, max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm
|
Signaling | Types of signaling: LED Floating signal contact Signal output: LED status indicator Signalization designation: DC OK Status display: LED Color: green DC OK: UOUT > 0.9 x UN (UN = 24ÃVÃDC)
|
Electrical properties | Number of phases: 3.00 Insulation voltage input/output: 3 kV AC (type test) 1.5 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 2100000 h (25ðC) > 1200000 h (40ðC) > 590000 h (60ðC) Insulation characteristics Protection class: I (in closed control cabinet) Degree of pollution: 2
|
Dimensions | Width: 42 mm Height: 130 mm Depth: 160 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm
|
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0 mm (ââ°¤ 40°C) 10 mm (ââ°¤ 70°C), vertically 50 mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Metal Type of housing: Aluminum (AlMg3) Hood version: Polycarbonate
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (>Ã2000Ãm, Derating: 10Ã%/1000Ãm) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 4g, 90 min.
|
Standards and regulations | Rail applications: ENÃ50121-4 Standard ââ¬Ã¢ Electronic equipment for use in electrical power installations and their assembly into electrical power installations: ENÃ50178/VDEÃ0160 (PELV) Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 62368-1Ã(SELV) Standard ââ¬Ã¢ Safety extra-low voltage: IEC 62368-1 (SELV) und ENÃ60204-1 (PELV) Standard - Safe isolation: DINÃVDEÃ0100-410 Standard - Safety of transformers: ENÃ61558-2-16 (air clearances and creepage distances only)
|
Approvals | UL approvals: UL Listed ULÃ508 UL/C-UL Recognized ULÃ60950-1 Conformity/Approvals SIL in accordance with IEC 61508: 0
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 4) Discharge in air: 8 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 3 kV (Test Level 3 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 1 - asymmetrical) Signal: 1 kV (Test Level 1 - symmetrical) Comments: Criterion B Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
|