PHOENIX CONTACT 2865340
PHOENIX CONTACT 2865340
PHOENIX CONTACTNon disponibile

MACX MCR-EX-SL-RPSSI-I - Power/input isolating amplifier

Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20mA signals from the Ex area to a load (active or passive) in the safe area. 3-way electrical isolation, SIL2 in accordance with IEC 61508, with screw connection
Cod. Articolo: 2865340
Cod. Fornitore: 2865340
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Repeater power supplies
Product family: MACX Analog
Application: Analog IN
No. of channels: 1
Type: Ex i signal conditioners with SIL functional safety
Electrical propertiesNo. of channels: 1
Electrical isolation: 3-way isolation
Electrical isolation between input and output: yes
Maximum power dissipation for nominal condition: 0.95 W (20ÂmA, 250ÂΩ)
Signal transmission behavior: InÂ=ÂOut
Step response (10-90%): < 200 µs (for jump 4 mA ... 20ÂmA, load 600 Ω)
< 600 µs (for jump 0 mA ... 20ÂmA, load 600 Ω)
Maximum temperature coefficient: < 0.01 %/K
Temperature coefficient, typical: < 0.004 %/K
Maximum transmission error: < 0.1 % (of final value)
Transmission error, typical: < 0.05 % (of final value)
Reverse polarity protection: yes
Electrical isolationâۉ€¹
Test voltage: 2.5 kV AC (50ÂHz, 60Âs)
Overvoltage category: II
Pollution degree: 2
Electrical isolation Input/output/power supply IEC/ENÂ61010-1
Standards/regulations: IEC/ENÂ61010-1
Rated insulation voltage: 300 Vrms
Insulation: Safe isolation
Electrical isolation Input/output IEC/ENÂ60079-11
Standards/regulations: IEC/ENÂ60079-11
Rated insulation voltage: 265 Vrms
Electrical isolation Input/power supply IEC/ENÂ60079-11
Standards/regulations: IEC/ENÂ60079-11
Rated insulation voltage: 265 Vrms
Electrical isolation Output/supply IEC/ENÂ60079-7
Standards/regulations: IEC/ENÂ60079-7
Rated insulation voltage: 265 Vrms
Supply
Designation: Repeater power supply operation
Nominal supply voltage: 24 VÂDC -20Â%Â...Â+25Â%
Supply voltage range: 19.2 VÂDC ... 30 VÂDC
Max. current consumption: < 76 mA (24ÂVÂDC / 20ÂmA / 1000ÂΩ)
< 55 mA (24ÂVÂDC / 20ÂmA / 250ÂΩ)
Power dissipation: < 1.1 W (24ÂVÂDC / 20ÂmA / 1000ÂΩ)
< 0.95 W (24ÂVÂDC / 20ÂmA / 250ÂΩ)
< 1.2 W (24ÂVÂDC / 20ÂmA / 0ÂΩ)
Power consumption: < 1.8 W (20ÂmA / 1000ÂΩ)
< 1.3 W (20ÂmA / 250ÂΩ)
Supplyâۉ€¹
Designation: Signal conditioner operation
Nominal supply voltage: 24 VÂDC -20Â%Â...Â+25Â%
Supply voltage range: 19.2 VÂDC ... 30 VÂDC
Max. current consumption: < 44 mA (24ÂVÂDC / 20ÂmA / 1000ÂΩ)
< 27 mA (24ÂVÂDC / 20ÂmA / 250ÂΩ)
Power dissipation: < 0.75 W (24ÂVÂDC / 20ÂmA / 1000ÂΩ)
< 0.65 W (24ÂVÂDC / 20ÂmA / 250ÂΩ)
< 0.95 W (24ÂVÂDC / 20ÂmA / 0ÂΩ)
Input dataSignal: Repeater power supply operation
Description of the input: Active current input, intrinsically safe
Number of inputs: 1
Input signal: Current
Current input signal: 4 mA ... 20 mA
Current limitation: 25 mA
Transmitter supply voltage: > 16 V (20ÂmA)
> 15.3 V (22.5 mA)
Polarization and surge protection: Yes
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Description of the input: Passive current input, intrinsically safe
Current input signal: 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop: < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Output dataAnalog
Number: 1
0
1
Type of output signal: Current
Output signal Current range: 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load Resistance: 1000 Ω (20ÂmA)
825 Ω (24ÂmA)
Output behavior in the event of an error: 0 mA (Cable break in the input)
Signal: Repeater power supply operation
Output description: Current output (active and passive)
Number of outputs: 1
Current output signal: 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output: < 1000 Ω (20ÂmA)
< 825 Ω (24ÂmA)
Output ripple: < 20 mVrms
Output behavior in the event of an error: 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Output description: Current output (active and passive)
Current output signal: 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output: < 1000 Ω (20ÂmA)
< 825 Ω (24ÂmA)
Output ripple: < 20 mVrms
Output behavior in the event of an error: 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Connection dataConnection method: Screw connection
Stripping length: 7 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
Test socket
Max. diameter: 2 mm
Ex dataEx installation (EPL): Gc
Div.Â2
Ex i circuits (EPL): Ga
Da
Ma
Div.Â1
Safety data: Repeater power supply operation
Max. output voltage Uo: 25.2 V
Max. output current Io: 93 mA
Max. output power Po: 587 mW
Safety-related maximum voltage Um: 253 VÂAC
125 VÂDC
I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co: 40 mH / 4.8 µF
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co: 26 mH / 2.9 µF
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co: 14 mH / 820 nF
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co: 3 mH / 107 nF
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co: 26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF
IIB/III (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co: 16 mH / 370 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co: 2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF
I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co: 37 mH / 0.54 µF, 0.35 mH / 1 µF, 0.009 mH / 2.9 µF, 0.001 mH / 4.15 µF
Safety data: Signal conditioner operation
Input voltage Ui: ≤ 30 V
Input current Ii: ≤ 150 mA
Max. internal inductance Li: negligible
Max. internal capacitance Ci: negligible
Safety-related maximum voltage Um: 253 VÂAC
125 VÂDC
InterfacesData communication (bypass)
HART function: Yes
Protocols supported: HART-transparent
SignalingStatus display: Green LED (supply voltage)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3edd36290ae8094db8e0add7aa964a6f/-S204x204-FJPG
Width: 12.5 mm
Height: 112.5 mm
Depth: 113.7 mm
Depth NSÂ35/7,5: 114.5 mm (Snapped onto DIN rail NSÂ35/7,5 in accordance with ENÂ60715)
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Housing material: PA 6.6-FR
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -40°C ... 60°C (Any mounting position)
-40°C ... 70°C (Derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Permissible humidity (operation): 10 % ... 95 % (non-condensing)
Altitude range (≤ 2000 m)
Altitude: ≤ 2000 m (The technical data refers to altitudes ≤2000Âm above mean sea level. For altitudes >2000Âm above mean sea level, refer to the data sheet.)
Ambient temperature (operation): -40°C ... 60°C
-40°C ... 70°C (Derating)
Rated insulation voltage: 375 VPP (Power supply, input / output)
Altitude range (≤ 3000 m)
Height range: > 2000 m ... 3000 m
Ambient temperature (operation): -40°C ... 54°C
-40°C ... 63°C (Derating)
Rated insulation voltage: 190 VÂAC (Power supply, input / output)
110 VÂDC (Power supply, input / output)
Altitude range (≤ 4000 m)
Height range: > 3000 m ... 4000 m
Ambient temperature (operation): -40°C ... 48°C
-40°C ... 56°C (Derating)
Rated insulation voltage: 60 V AC/DC (Power supply, input / output)
Altitude range (≤ 5000 m)
Height range: > 4000 m ... 5000 m
Ambient temperature (operation): -40°C ... 42°C
-40°C ... 49°C (Derating)
Rated insulation voltage: 60 V AC/DC (Power supply, input / output)
ApprovalsCE
Certificate: CE-compliant
Note: and ENÂ61326
ATEX
Identification: ïÃ‹œ II (1) G [Ex ia Ga] IIC
ïÃ‹œ II (1) D [Ex ia Da] IIIC
ïÃ‹œ II 3(1) G Ex ec [ia Ga] IIC T4 Gc
ïÃ‹œ I (M1) [Ex ia Ma] I
Certificate: BVS 08 ATEX E 054X
IECEx
Identification: [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
Certificate: IECEx BVS 08.0016X
CCCÂ/ÂChina-Ex
Identification: [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
Certificate: 2022122316115973
UL, USA/Canada
Identification: UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Div. 2, Groups IIC, IIB, IIA T4
Associated apparatus for use in Class I, Division 1, Groups A,B,C,D
Associated apparatus for use in Class II, Div.1 Groups E,F,D
Associated apparatus for use in Class III, Division 1
Associated apparatus for use in Class I, Zone 0,1,2, Groups IIC,IIB,IIA
Certificate: ïÃ¢€¢, C.D.-No 83104549
UL, USA/Canadaâۉ€¹
Identification: UL 61010 Listed
Class I Div 2; IS for Class I, II, III Div 1
Certificate: ïÃ¢€¢, C.D.-No 83104549
Shipbuilding approval
Certificate: DNV GL TAA000020C
Safety Integrity Level (SIL, IEC 61508)
Identification: 2
Certificate: IN-AT-AS-MRL-2300149
Systematic Capability
Identification: 3
KC-s
Identification: [ExÂia]ÂIIC/IIB
Certificate: 17-KA4BO-0400X
INMETRO
Identification: [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
Certificate: DNV 18.0136 X
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: ENÂ61000-4-3
Typical deviation from the measuring range final value: 1 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Typical deviation from the measuring range final value: 1 %
Conducted interference
Designation: Conducted interferences
Standards/regulations: ENÂ61000-4-6
Typical deviation from the measuring range final value: 1 %
Standards and regulationsElectrical isolation: 3-way isolation
GBÂStandard
Standards/regulations: GB/TÂ3836.1
GB/TÂ3836.3
GB/TÂ3836.4
MountingMounting type: DIN rail mounting
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00369.pdf

Approvals_01141.pdf

Approvals_01143.pdf

Approvals_01225.pdf

Approvals_01825.pdf

Data_sheet_03595.pdf

Manual_00026.pdf

Manufacturer_declaration_00518.pdf

Manufacturer_declaration_15279.pdf

Manufacturer_declaration_17787.pdf

Package_slip_01533.pdf

Technical_drawing_38999.pdf