S-PT1-2PE-24DC - Surge protection device

Screw on module for conduit systems, with two conductor protection for a 2-core floating signal circuit. Design: 24 V DC
Cod. Articolo: 2818122
Cod. Fornitore: 2818122
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Caratteristiche Tecniche
NotesTrade restriction
CE note: The products are offered exclusively for export outside the EU and the European Economic Area.
Product propertiesProduct family: SURGETRAB
IEC test classification: C1
C2
C3
D1
Type: Screw-in module
Number of positions: 3
Surge protection fault message: none
Electrical propertiesNominal voltage UN: 24 V DC
Connection dataConnection method: Screw connection
Conductor cross section flexible min.: 0.14 mm²
Conductor cross section flexible max.: 1.5 mm²
Conductor cross section, rigid min.: 0.14 mm²
Conductor cross section, rigid max.: 1.5 mm²
DimensionsDimensional drawing: https://caas.phoenixcontact.com/caas/v1/stable/media/85174/full/b1500?format=jpg
Width: 33 mm
Height: 33 mm
Depth: 120 mm
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitDirection of action: Line-Line & Line-Earth Ground
Maximum continuous voltage UC: 28 V DC
20 V AC
Maximum continuous voltage UC (line-line): 28 V DC
20 V AC
Operating effective current IC at UC: ≤ 5 µA
Residual current IPE: ≤ 2 µA
Nominal discharge current In (8/20) µs (line-line): 10 kA
Nominal discharge current In (8/20) µs (line-ground): 10 kA
Total surge current (8/20) µs: 20 kA
Max. discharge current Imax (8/20) µs maximum (line-line): 10 kA
Max. discharge current Imax (8/20) µs maximum (line-earth): 10 kA
Nominal pulse current Ian (10/1000) µs (line-line): 180 A
Nominal pulse current Ian (10/1000) µs (line-earth): 180 A
Output voltage limitation at 1 kV/µs (line-line) spike: ≤ 60 V
Output voltage limitation at 1 kV/µs (line-earth) spike: ≤ 450 V
Output voltage limitation at 1 kV/µs (line-line) static: ≤ 60 V
Residual voltage at In (conductor-conductor): ≤ 40 V
Residual voltage at In (conductor-ground): ≤ 60 V
Residual voltage with Ian (10/1000) µs (line-line): ≤ 25 V
Residual voltage with Ian (10/1000) µs (line-earth): ≤ 20 V
Voltage protection level Up (line-line): ≤ 55 V
Voltage protection level Up (line-earth): ≤ 550 V
Response time tA (line-line): ≤ 1 ns
Response time tA (line-earth): ≤ 100 ns
Input attenuation aE, sym.: ≤ 1.6 dB (up to 500 kHz, 50 Ω system)
≤ 0.6 dB (up to 200 kHz, 150 Ω system)
≤ 0.2 dB (up to 50 kHz, 600 Ω system)
Cut-off frequency fg (3 dB), sym. in 50 Ω system: typ. 3.5 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ω system: typ. 1.5 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ω system: typ. 400 kHz
Capacity (Core-Core): typ. 1.5 nF
Resistance per path: 10 Ω 5 %
Surge protection fault message: none
Impulse durability (line-line): C2 - 10 kV / 5 kA
Impulse durability (line-earth): C2 - 10 kV / 5 kA
D1 - 2.5 kA
Alternating current carrying capacity (line-earth): 5 A - 1 s
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP40
Ambient temperature (operation): -40 °C ... 80 °C
ApprovalsConformity/Approvals
UL, USA / Canada: Class I, Div. 2, Groups A, B, C, D
Standards and regulationsAir clearances and creepage distances
Standards/regulations: VDE 0110-1 / IEC 60664-1
Standards Information technology specification
Standards/regulations: IEC 61643-21
MountingMounting type: Connection-specific intermediate plugging
Descrizione
S-PT1-2PE-24DC SPD segnale