MACX MCR-UI-UI-UP-NC - Signal conditioner

Isolating amplifier with safe electrical isolation and wide-range power supply (24 V ... 230 V AC/DC). DIP switches on the front, over 1600 signal conversions can be set. Standard configuration (IN 0 ... 10 V/OUT 0 ... 20 mA), screw connection, SIL.
Cod. Articolo: 2811297
Cod. Fornitore: 2811297
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Signal conditioner
Product family: MACX Analog
No. of channels: 1
Type: Signal conditioners with SIL functional safety
Configuration: DIP switches
Electrical propertiesAlignment span: ± 4 %
Alignment zero: ± 4 %
No. of channels: 1
Electrical isolation between input and output: yes
Limit frequency (3 dB): 10 kHz (Can be switched to 30 Hz)
Maximum power dissipation for nominal condition: < 0.9 W (20mA)
Protective circuit: Transient protection
Step response (10-90%): 35 µs (10kHz)
11 ms (30Hz)
Maximum temperature coefficient: 0.0075 %/K
Maximum transmission error: ≤ 0.1 % (Compared to the final value)
Electrical isolation
Test voltage: 2.5 kV AC (50Hz, 60s)
Overvoltage category: II
Pollution degree: 2
Electrical isolation Input/output/power supply IEC/EN61010-1
Standards/regulations: IEC/EN61010-1
Rated insulation voltage: 300 Vrms
Insulation: Safe isolation
Electrical isolation Input/output/power supply IEC/EN60079-7
Standards/regulations: IEC/EN60079-7
Rated insulation voltage: 275 V
Supply
Nominal supply voltage range: 24 V AC/DC ... 230 V AC/DC -20%...+10% (50/60Hz)
Supply voltage range: 19.2 V AC/DC ... 253 V AC/DC (50/60Hz)
Power dissipation: < 0.8 W (at 24 V DC / 20 mA)
< 0.9 W (At 230 V AC / 20 mA)
Input dataSignal: Voltage/current
Number of inputs: 1
Voltage input signal: 0 mV ... 50 mV
0 mV ... 60 mV
0 mV ... 75 mV
0 mV ... 100 mV
0 mV ... 120 mV
0 mV ... 150 mV
0 mV ... 200 mV
0 mV ... 300 mV
0 mV ... 500 mV
0 V ... 1 V
0 V ... 1.5 V
0 V ... 2 V
0 V ... 3 V
0 V ... 5 V
0 V ... 10 V (Configurable via DIP switches)
0 V ... 15 V
0 V ... 20 V
0 V ... 30 V
0 V ... 50 V
0 V ... 100 V
-50 mV ... 50 mV
-60 mV ... 60 mV
-75 mV ... 75 mV
-100 mV ... 100 mV
-120 mV ... 120 mV
-150 mV ... 150 mV
-200 mV ... 200 mV
-300 mV ... 300 mV
-500 mV ... 500 mV
-1 V ... 1 V
-1.5 V ... 1.5 V
-2 V ... 2 V
-3 V ... 3 V
-5 V ... 5 V
-10 V ... 10 V
-15 V ... 15 V
-20 V ... 20 V
-30 V ... 30 V
-50 V ... 50 V
-100 V ... 100 V
1 V ... 5 V
2 V ... 10 V
Min. voltage input signal: ± 50 mV
Max. voltage input signal: ± 100 V
Current input signal: 0 mA ... 1 mA (Configurable via DIP switches)
0 mA ... 1.5 mA
0 mA ... 2 mA
0 mA ... 3 mA
0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 15 mA
0 mA ... 20 mA
0 mA ... 30 mA
0 mA ... 50 mA
0 mA ... 100 mA
-1 mA ... 1 mA
-1.5 mA ... 1.5 mA
-2 mA ... 2 mA
-3 mA ... 3 mA
-5 mA ... 5 mA
-10 mA ... 10 mA
-15 mA ... 15 mA
-20 mA ... 20 mA
-30 mA ... 30 mA
-50 mA ... 50 mA
-100 mA ... 100 mA
1 mA ... 5 mA
2 mA ... 10 mA
4 mA ... 20 mA
Minimum current input signal: ± 1 mA
Max. current input signal: ± 100 mA
Input resistance of voltage input: approx. 1 MΩ (±1VDC... ±100VDC)
Input resistance current input: approx. 10 Ω (±10mADC...±100mADC)
Output dataSignal: Voltage/current
Number of outputs: 1
Configurable/programmable: Yes, can be switched
Voltage output signal: 0 V ... 10 V (Configurable via DIP switches)
0 V ... 5 V
2 V ... 10 V
1 V ... 5 V
-10 V ... 10 V
-5 V ... 5 V
0 V ... 2.5 V
0.5 V ... 2.5 V
-2.5 V ... 2.5 V
Max. voltage output signal: 15 V
Output signal voltage inverse: 0 V ... 2.5 V
0 V ... 5 V
0 V ... 10 V
Current output signal: 0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 20 mA (Configurable via DIP switches)
1 mA ... 5 mA
2 mA ... 10 mA
4 mA ... 20 mA
-5 mA ... 5 mA
-10 mA ... 10 mA
-20 mA ... 20 mA
Max. current output signal: 35 mA
Output signal current inverse: 0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 20 mA
Load/output load voltage output: ≥ 1 kΩ (10V)
Load/output load current output: ≤ 600 Ω (20 mA; active)
passive: ≤ (UB-2 V) / Ioutmax
Ripple: < 10 mVrms
Connection dataConnection method: Screw connection
Stripping length: 7 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
Test socket
Max. diameter: 2 mm
Ex dataEx installation (EPL): Gc
Div.2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3edd36290ae8094db8e0add7aa964a6f/-S204x204-FJPG
Width: 12.5 mm
Height: 112.5 mm
Depth: 113.7 mm
Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715)
Material specificationsHousing material: PA 6.6-FR
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -20°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude range (≤ 2000 m)
Altitude: ≤ 2000 m (The technical data refers to altitudes ≤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.)
Ambient temperature (operation): -20°C ... 70°C
Safety-related maximum voltage Um: 275 V
Altitude range (≤ 3000 m)
Height range: > 2000 m ... 3000 m
Ambient temperature (operation): -20°C ... 60°C
Safety-related maximum voltage Um: 190 V
Altitude range (≤ 4000 m)
Height range: > 3000 m ... 4000 m
Ambient temperature (operation): -20°C ... 55°C
Safety-related maximum voltage Um: 60 V
Altitude range (≤ 5000 m)
Height range: > 4000 m ... 5000 m
Ambient temperature (operation): -20°C ... 45°C
Safety-related maximum voltage Um: 60 V
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex nA IIC T4 Gc
Certificate: BVS09ATEXE028X
UKCAEx(UKEX)
Identification:  II 3 G Ex nA IIC T4 Gc
Certificate: PxCIF21UKEX2811459X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECExBVS09.0013X
CCC/China-Ex
Identification: Ex ec IIC T4 Gc
Certificate: 2021122304114078
UL, USA/Canada
Identification: UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Shipbuilding approval
Certificate: DNV GL TAA00000AG
Safety Integrity Level (SIL, IEC 61508)
Identification: 2
INMETRO
Identification: Ex ec IIC T4 Gc
Certificate: DNV 21.0125 X
EAC Ex
Identification:  2Ex ec IIC T4 Gc
Certificate: BY/112 02.01 TP012 103.01 00078
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: B
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 1.9 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 2 %
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 4.6 %
Standards and regulationsGBStandard
Standards/regulations: GB/T3836.1
GB/T3836.3
MountingMounting type: DIN rail mounting
Mounting position: any
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01155.pdf

Approvals_01156.pdf

Approvals_01172.pdf

Approvals_01518.pdf

Approvals_01709.pdf

Data_sheet_03462.pdf

Manual_00026.pdf

Manufacturer_declaration_00545.pdf

Manufacturer_declaration_01826.pdf

Manufacturer_declaration_15087.pdf

Manufacturer_declaration_17787.pdf

Package_slip_01576.pdf

Technical_drawing_38608.pdf