Electrical properties | Maximum power dissipation for nominal condition: 8.7 W Transmission medium: Copper Potentials: Communications power (U Supply voltage: 7.5 VÃDC (see safety data) Current draw: max. 360 mA Potentials: Main circuit supply (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including ripple) Current draw: typ. 30 mA Potentials: Segment circuit supply (U Supply voltage: 24 V Supply: Module electronics Supply voltage: 24 VÃDC (via voltage jumper) Supply voltage range: 19.2 VÃDC ... 30 VÃDC Electrical isolation/isolation of the voltage ranges Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics): 500 VÃAC, 50 Hz, 1 min. Test voltage: 7.5 V supply (bus logic)/24 V supply (UM, US), GND, clock outputs, relay outputs, FE: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply (UM, US), GND, clock outputs/7.5 V supply (bus logic), relay outputs: 500 VÃAC, 50 Hz, 1 min. Test voltage: COMBICON X3 relay outputs/COMBICON X4 relay outputs, Inline connector relay outputs,7.5 V supply (bus logic), 24 V supply (UM, US), GND, clock outputs, FE: 2500 VÃAC, 50 Hz, 1 min. Test voltage: COMBICON X4 relay outputs/COMBICON X3 relay outputs, Inline connector relay outputs,7.5 V supply (bus logic), 24 V supply (UM, US), GND, clock outputs,: 2500 VÃAC, 50 Hz, 1 min.
|