PHOENIX CONTACT 1148699
PHOENIX CONTACT 1148699
PHOENIX CONTACTDisponibile

RIF-RPT-LDP-24DC/2X2/2X1/AU/FG - Relay Module

Relay module with Push-in connection, consisting of: relay base with status LED, freewheeling diode, and retaining bracket, safety relay with force-guided contacts in accordance with DINEN61810-3, contact switching type: 2N/O contacts and 2N/C contacts, input voltage: 24VDC
Cod. Articolo: 1148699
Cod. Fornitore: 1148699
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Relay Module
Product family: RIFLINEcomplete
Operating mode: 100% operating factor
Mechanical service life: approx. 107 cycles
B10d: 810000 Cycles (AC15, 250V/0.5A, 1NO)
170000 Cycles (AC15; 250V/2A; 1NO)
318000 Cycles (DC13, 24V/1A, 1NO)
208000 Cycles (DC13, 24V/2A, 1NO)
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation: Basic insulation
Safe isolation, reinforced insulation and 6 kV between coil and contact circuit and between contacts 11-12 and 13-14, 41-42 to 23-24, 33-34
Overvoltage category: III
Pollution degree: 2
Electrical propertiesMaximum power dissipation for nominal condition: 0.41 W
Test voltage (Winding/contact): 4 kVrms (50Hz, 1min., winding/contact)
Test voltage (): 1.5 kVrms (50Hz, 1min., open contact)
2.5 kVrms (50Hz, 1min., between contacts: 7, 8 to 9, 10)
4 kVrms (50Hz, 1min., between contacts: all others)
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC (Input/output)
Rated surge voltage: 6 kV (Input/output)
Short-circuit protection device
Current: 10 A (RT28-32)
Voltage: 500 V (SCPD)
Short-circuit current: 1 kA (conditional short-circuit current)
Input dataCoil side
Nominal operating voltage UN: 24 VDC
Input voltage range in reference to UN: See derating diagram
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 17 mA
Input power dissipation for UN: 0.4 W
Typical response time: 10 ms
Typical release time: 15 ms
Coil voltage: 24 VDC
Protective circuit: Freewheeling diode
Status display: Yellow LED
Output dataSwitching
Contact switching type: 2 N/O contacts, 2 N/C contacts
Type of switch contact: Single contact
Contact material: AgSnO, hard gold-plated
Maximum switching voltage: 250 VAC
300 VDC
Minimum switching voltage: 10 V (5 mA)
Limiting continuous current: 6 A
Maximum inrush current: 35 A (20ms)
Min. switching current: 5 mA (10V)
Interrupting rating (ohmic load) max.: 144 W (24VDC)
100 W (48VDC)
75 W (60VDC)
55 W (110VDC)
50 W (220VDC)
1500 VA (250VAC)
Force-guided contacts in accordance with EN61810-3: TypeA
Utilization category CB Scheme (IEC 60947-5-1): AC15, 2 A/240 V (N/O contact)
DC13, 2 A/24 V (N/O contact)
Connection dataConnection method: Push-in connection
Stripping length: 8 mm
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG: 26 ... 16 (solid)
26 ... 16 (flexible)
DimensionsWidth: 21 mm
Height: 96 mm
Depth: 67 mm
Material specificationsFlammability rating according to UL 94: V2 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Relay): RT II (Relay)
Degree of protection (Installation location): IP54 (Installation location)
Ambient temperature (operation): -40°C ... 60°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
ApprovalsUKCA
Certificate: UKCA-compliant
Standards and regulationsAll specifications in accordance with the standard
Standards/regulations: IEC 60947-5-1
IEC 61810-3
Air clearances and creepage distances between the power circuits
Standards/regulations: EN61810-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Manufacturer_declaration_01296.pdf

Manufacturer_declaration_03187.pdf

Manufacturer_declaration_06592.pdf

Package_slip_02199.pdf

Product_information_00033.pdf

Product_information_00087.pdf

Technical_drawing_09304.pdf