Number of contacts as normally closed contact | 1 |
Number of contacts as normally open contact | 0 |
Rated operational current (Ie) | 3 A @ 24V, 120V, AC-15 per IEC/EN 60947-5-1 for utilization category |
Rated operation current Ie at AC-15, 230 V | 1.5 A |
Rated impulse withstand voltage (Uimp) | 6 kV |
Conventional free-air thermal current Ith | 5 A |
AC thermal rated current | 5 A |
DC maximum volt-ampere | 28 VA |
Duty time | 100 % |
DC thermal rated current | 2.5 A |
Rated frequency | 50/60 Hz |
Insulation voltage (Ui) | Rated 250V |
Switching capacity, min | 17V DC/5 mA |
Short-circuit protective device | 10 A Type gG |
Rated operating voltage (Ue) | 250V AC/250V DC |
AC maximum volt-ampere | Making: 3600VA, Breaking: 360VA |
Mounting | Front |
Pilot duty | B300, R300 |
Pollution degree | 3 |
Ambient air temperature | Operation: -25... +60 ðC, Storage: -50 ... +80 ðC |
Number of operations | 50000 cycles |
Resistance to shock | 25 G/11 ms per IEC 60068-2-27 |
Resistance to vibration | 5 G/3 ... 150 Hz per IEC 60068-2-6 |
Standards compliance | IEC: IEC/EN 60947ââ¬Ã¢1, IEC/EN 60947-5-1, UL/cULus: UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1 |